Controller Use
Parameter number 14:
Switch_HighPressure_Logical:
This parameter has the purpose of changing the N.O or N.C
direction of the high pressure switch, to change the value of this
parameter simply press the dial and turn the dial to the right until
the active value changes or in case you want to deactivate the
parameter simply turn the dial to the left and change the value to
inactive in any of the two values you want simply press the dial so
that the value is saved.
Parameter number 15:
Switch_FlowWater_Logical:
The purpose of this parameter is to change the N.O or N.C
direction of the water flow switch, to change the value of this
parameter simply press the dial and turn the dial to the right until
the active value changes or in case you want to deactivate the
parameter simply turn the dial to the left and change the value to
inactive in any of the two values you want simply press the dial so
that the value is saved.
Parametr numbre 16:
Switch_OnOff_Value:
With this parameter you can see the current value of the on/off
switch input of the system.
www.comfort-flex.com
Parameter number 17:
Switch_LowPressure_Value:
This parameter shows the current value of the low pressure
switch input.
Parameter number 18:
Switch_HighPressure_Value:
This parameter shows the current value of the high pressure
switch input.
Parameter number 19:
Switch_FlowWater_Value:
This parameter shows the current value of the water flow switch
input.
51
iom-cliv-eng