Parameter number 9:

Timer_Stop_Pump:

This parameter is intended to modify the water pump shutdown
time after the power off button has been activated to completely
stop the system.
Parameter number 10:
Alarm_Indicator:
The purpose of this parameter is to indicate if there is an active
alarm, in this case the value of this alarm is currently set to
deactivated, but at any time an alarm occurs it will change to
activated.
Parameter number 11:
Reset_Alarm:
This parameter has the purpose of deleting the alarms that are
active, for this case it is currently deactivated to activate it simply
press the dial and turn it clockwise to change it to active mode,
after it changes to active mode press the dial again and turn it
counterclockwise to change it to inactive mode.
It must be considered that in case an alarm is present and has
not been deleted this procedure will not work, so you will have
to check in the alarms section the alarm number that the system
presents so that it can be deleted.
iom-cliv-eng
Parameter number 12:
Switch_OnOff_Logical:
With this parameter you can change the N.O or N.C direction of
the power switch located on the front of the panel to change the
value of this parameter simply press the dial and turn the dial to
the right until the active value changes or in case you want to
deactivate the parameter simply turn the dial to the left and you
have to change the value to inactive in any of the two values you
want simply press the dial to save the value.
Parameter number 13:
Switch_LowPressure_Logical:
This parameter has the purpose of changing the N.O or N.C
direction of the low pressure switch, to change the value of this
parameter simply press the dial and turn the dial to the right until
the active value changes or in case you want to deactivate the
parameter simply turn the dial to the left and change the value to
inactive in any of the two values you want simply press the dial so
that the value is saved.
50