Samson TROVIS 5724-8 Mounting And Operating Instructions page 74

Without/with fail-safe action electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

Annex A
CO/PA
Function/
designation
Universal input I4
I4
Function
AI4.I1
Input signal, point 1
AI4.COR
Offset AI4
 1)
AI4.O1
Output signal, point 1
AI4.I2
Input signal, point 2
AI4.O2
Output signal, point 2
Switching output
M4
Function
M4.T
Lag time
M5
Logic
Parameters are listed in Service folder > Start-up.
1)
16-2
Setting/
adjustment range
0: None
1: DI4 not inverted
2: DI4 inverted
4: AI4 (0 to 10 V)
0.0 to 99.9 %
–9.9 to +9.9 %
–50 to +150 °C
0.1 to 100.0 %
–50 to +150 °C
0:
None
1:
On with LIM1/Off with lag time
2:
On with LIM2/Off with lag time
3:
On at travel > 0 %/Off at 0 % with lag time
4:
On at travel < 100 %/Off at 100 % with lag time
5:
Alarm active
6:
Fixed actuator positioning value [1] reached
7:
Fixed actuator positioning value [2] reached
8:
Manual mode active
0 to 999 s
0:
Not inverted
1:
Inverted
EB 5724-8 EN