Firmware Versions - Samson TROVIS 5724-8 Mounting And Operating Instructions

Without/with fail-safe action electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

2.3 Firmware versions

Firmware revisions
Old
New
2.00
2.01
Communication parameters that cannot be changed are hidden.
2.01
2.10
Automatic protocol detection works with SSP and Modbus. In this case, Modbus is re-
stricted to the setting '9600, 8N1'.
The 'Communication module' and 'Protocol' communication parameters have been re-
placed by the communication parameter with same name (i.e. 'Protocol' but with different
setting options. The new settings are 'None', 'Automatic (SSP, Modbus)' and 'Modbus
(adjustable)'. 'Automatic (SSP, Modbus)' is set by default.
The message 'Last positioning value upon signal failure' has been replaced by 'Last
travel value'. The electric actuator with process controller stops immediately upon signal
failure with this setting.
Transit time measurement and initialization can be canceled by pressing the [0] key. The
electric actuator with process controller does not perform a zero calibration after cancel-
lation. The actuator moves to a predefined positioning value.
2.10
2.11
New system code numbers: 2, 38 and 58
'LIM1', 'LIM2', '[I]/[O] keys or LIM1' and '[I]/[O] keys or LIM2' have been added to the
Trigger function (A1.5).
The error message 'Eb' is displayed at the actuator when a bus failure is detected.
Baud rate 38400 is no longer available for Modbus.
2.11
2.12
The system code numbers are assigned in the range from 0 to 99.
EB 5724-8 EN