Technical Data - Samson 2404-2 Mounting And Operating Instructions

Excess pressure cwith pilot valve
Table of Contents

Advertisement

Design and principle of operation

3.2 Technical data

The nameplates for the components used
provide information on the component ver-
sions (see the 'Markings on the device' sec-
tion).
Note
More information is available in Data Sheet
u T 2540.
Conformity
The Type 2404-2 Regulator bears both the
CE and EAC marks of conformity.
Process medium and scope of application
The Type 2404-2 Excess Pressure Valve with
pilot valve for small set point ranges is used
to maintain the tank pressure to an adjusted
set point.
− For gases
− Medium temperature range
–5 to +195 °F/–20 to +90 °C
− Set points
0.075 to 3 psi/5 to 200 mbar
− Valve sizes
NPS 2½ to 16/DN 65 to 400
− Pressure rating
Class 125, 150, 300/PN 16, 40
3-4
Leakage class
The soft-seated regulator has the leakage
class IV according to IEC 60534-4.
Noise emissions
SAMSON is unable to make general state-
ments about noise emissions. The noise emis-
sions depend on the regulator version, plant
facilities, process medium and operating
conditions.
Dimensions and weights
Table 3-8 and Table 3-9 provide an over-
view of the dimensions and weights. The
lengths and heights in the dimensional draw-
ings are shown on page 3-9 onwards.
EB 2540 EN