3.5 Technical data

The nameplates on the valve and actuator
provide information on the control valve ver-
sion. See the 'Markings on the device' sec-
tion.
Note
More information is available in Data Sheets
u T 8012 and u T 8012-2.
Conformity
The Type 3241 Valve bears the CE, UKCA
and EAC marks of conformity.
Temperature range
Depending on the version, the control valve
is designed for a temperature range from
–10 to +220 °C (14 to 428 °F). The use of
an insulating section or bellows seal can ex-
tend the temperature range from –196 to
+450 °C (–325 to +842 °F) depending on
the properties of the materials used.
Leakage class
Depending on the version, the following
leakage class applies:
Seal (12 on name-
plate)
Pressure balancing
(14 on nameplate)
Leakage class (ac-
cording to ANSI/
FCI 70-2)
EB 8012 EN
ME, ST
ME, ST
PT, PK
D/B
Min. IV
Min. IV
Noise emissions
SAMSON is unable to make general state-
ments about noise emissions. The noise emis-
sions depend on the valve version, plant fa-
cilities and process medium.
Optional RFID tag
Application range according to the technical
specifications and the explosion protection
certificates. These documents are available
on our website at u www.samsongroup.com
> Service & Support > Electronic nameplate.
VI