Riello RDB2.2 FIREBIRD C20 70K DGT Installation, Use And Maintenance Instructions

Riello RDB2.2 FIREBIRD C20 70K DGT Installation, Use And Maintenance Instructions

Kerosene burner
Table of Contents

Advertisement

Installation, use and maintenance instructions
Kerosene burner
One stage operation
CODE
MODEL
TYPE
20034605
RDB2.2 FIREBIRD C20 70K DGT
744LD2X
20035283 (4) - 08/2015

Advertisement

Table of Contents
loading

Summary of Contents for Riello RDB2.2 FIREBIRD C20 70K DGT

  • Page 1 Installation, use and maintenance instructions Kerosene burner One stage operation CODE MODEL TYPE 20034605 RDB2.2 FIREBIRD C20 70K DGT 744LD2X 20035283 (4) - 08/2015...
  • Page 3: Table Of Contents

    Contents Declaration....................................3 Information and general warnings............................4 Information about the instruction manual........................4 2.1.1 Introduction ..................................4 2.1.2 General dangers ................................4 2.1.3 Other symbols................................. 4 2.1.4 Delivery of the system and the instruction manual ......................5 Guarantee and responsibility ............................5 Guidance for the use of bio fuel blends up to 30% where gas oil use is permitted by the appliance Manufacturer ..
  • Page 4 Contents 8.8.3 Shutdown test................................24 8.8.4 Diagnosis of the flame signal quantity ...........................24 8.8.5 Intermittent operation ..............................24 8.8.6 Recycle and limit of repetitions............................24 8.8.7 Presence of an extraneous light or parasite flame ......................24 8.8.8 Pre and post spark ignition ............................24 8.8.9 External lockout signal ..............................24 8.8.10 Limitations in the control of the heat request thermostat (HT) ..................25 8.8.11 Reset protection ................................25 8.8.12 Frequency supply error ..............................25...
  • Page 5: Declaration

    Address: Via Pilade Riello, 7 37045 Legnago (VR) Product: Kerosene burner Model: RDB2.2 FIREBIRD C20 70K DGT These products are in compliance with the following Technical Standard: EN 12100 EN 267 and according to the European Directives: 2006/42/EC Machine Directive...
  • Page 6: Information And General Warnings

    Information and general warnings Information and general warnings Information about the instruction manual 2.1.1 Introduction DANGER: EXPLOSION The instruction manual supplied with the burner: This symbol signals places where an explosive at-  is an integral and essential part of the product and must not mosphere may be present.
  • Page 7: Delivery Of The System And The Instruction Manual

    All components within the hydraulic circuit suitable for burner is integral and complete. bio fuel use and supplied by Riello will be identified as Bio com- patible. No warranty is given in relation to the use of components Failure to observe the information given in this which are not so identified with bio fuel blends.
  • Page 8: Guidance For The Use Of Bio Fuel Blends Up To 30% Where Gas Oil Use Is Permitted By The Appliance Manufacturer

    Quality Control and In no event shall Riello (and its subsidiaries) be liable for any in- management system to ensure high standards are maintained direct, incidental, special or consequential damages including, within the storage, blending and delivery processes.
  • Page 9: Safety And Prevention

    Safety and prevention Safety and prevention Introduction The burners have been designed and built in compliance with which the burner has been regulated, the pressurisation of the current regulations and directives, applying the known technical combustion chamber, the dimensions of the combustion cham- rules of safety and envisaging all the potential danger situations.
  • Page 10: Personnel Training

    Safety and prevention Personnel training The user is the person, body or company that has acquired the machine and intends to use it for the specific purpose. He is re- sponsible for the machine and for the training of the people work- ing around it.
  • Page 11: Technical Description Of The Burner

    Screw of by-pass pump ............No. 1 Bio blend, it will be essential to use flexible oil Plastic air cover ..............No. 1 lines suitable for bio fuel use. 5 pin plug................No. 1 Please contact Riello for further information. 20035283...
  • Page 12: Burner Dimensions

    Technical description of the burner Burner dimensions Flange Burner ø 75 D4087 Fig. 2 20035283...
  • Page 13: Installation

    Installation Installation Notes on safety for the installation After carefully cleaning all around the area where the burner will The installation of the burner must be carried out be installed, and arranging the correct lighting of the environ- by qualified personnel, as indicated in this manual ment, proceed with the installation operations.
  • Page 14: Installer/Servicer Notes For The Use Of Gas Oil With Bio Blends Up To 30% Where Gas Oil Use Is Permitted By The Appliance Manufacturer

    30%" within the burner technical manual). be suitable for bio fuel use (check with Riello if in doubt).  If a Bio blend is in use the installer must seek information...
  • Page 15: Boiler Fixing

    Installation Boiler fixing  Put on the flange 1)(Fig. 5) the screw and two nuts.  Fix the flange 1)(Fig. 6) to the boiler door 4) using screws 2) and (if necessary) the nuts 3) interposing the insulating gas- ket 5). The seal between burner and boiler must be airtight.
  • Page 16 Installation The combustion air supply is through a flexible or rigid pipe con- nected to the air intake. Consequently, you must comply with the following requirements and instructions:  The combustion air intake tube must be: - fastened securely to the burner; - made of a suitable material, with temperature characteris- tics in the range - 30 °C to 80 °C;...
  • Page 17: Hydraulic Systems

    In case of use with gas oil containing up to 30% Bio blend, it will be essential to use flexible oil lines suitable for bio fuel use. WARNING Please contact Riello for further information. D10934 Fig. 12 Key (Fig. 12)
  • Page 18: One Pipe System

    Usually the tank is lower than the burner. You are advised to use additional filters on the fuel supply line. Riello recommends a good quality fuel filter at the CAUTION tank (Fig. 13 - Fig. 14) and a secondary filter (60 ...
  • Page 19: Two Pipe System

    You are advised to use additional filters on the fuel supply line. Riello recommends a good quality fuel filter at the CAUTION tank (Fig. 15) and a secondary filter (60  for gas oil and 15  for kerosene) are used to protect the burner pump and nozzle from contamination.
  • Page 20: Electrical System

    Electrical system Electrical system Notes on safety for the electrical wiring  The electrical wiring must be carried out with the electrical supply disconnected.  Electrical wiring must be carried out by qualified personnel and in compliance with the regulations currently in force in the country of destination.
  • Page 21: Electrical Wiring

    Electrical system Electrical wiring 7.2.1 Control box ~ 50Hz - 230V This operation must be performed with the burner turned off and mains power disconnected. DANGER Main switch All the installation, maintenance and dismantling operations should be performed voltage free. The replacement of the control box must be per- DANGER formed by qualified personnel, as indicated in this...
  • Page 22: Start-Up, Calibration And Operation Of The Burner

    Start-up, calibration and operation of the burner Start-up, calibration and operation of the burner Notes on safety for the first start-up The first start-up of the burner must be carried out Check the correct working of the adjustment, com- by qualified personnel, as indicated in this manual mand and safety devices.
  • Page 23: Pump Pressure

    Start-up, calibration and operation of the burner Pump pressure The pump leaves the factory set for kerosene working. 10 bar: maximum pressure for kerosene. Air damper adjustment The air damper is set in factory. This regulation is purely indica- tive. Each installation however, has its own unpredictable working conditions: actual nozzle output;...
  • Page 24: Operation Programme

    Start-up, calibration and operation of the burner Operation programme Normal operation Lockout due to ignition failure D11212 D11210 POWER PO W ER SUPPLY POW ER SUPPLY POWER SUPPLY SUPPLY Lockout Lockout Green blink Green Blinking Orange Blinking Green Green Green Green blinking blink Orange...
  • Page 25: Table Of Times

    Start-up, calibration and operation of the burner Table of times Symbol Description Value (sec.) Standby: the burner is waiting for a heat request  1 Standby time for an input signal: reaction time, control box remains in waiting status for t1 Initialisation check time: interval time for checking the activation of the main power supply Checks extraneous light during t2: waiting mode for t2l, then lockout: the motor does not start Pre-purge time: the fan motor is working...
  • Page 26: Shutdown Test

    Start-up, calibration and operation of the burner 8.8.3 Shutdown test 8.8.7 Presence of an extraneous light or parasite flame If, during operations, the reset push-button is pressed for longer than 5 seconds and less than 10 seconds, (so as not to go to the The presence of the parasite flame or the extraneous light can be next menu) the burner switches off, the oil valve closes, the flame detected in the stand-by condition when the burner is stopped...
  • Page 27: Limitations In The Control Of The Heat Request Thermostat (Ht)

    Start-up, calibration and operation of the burner  If the anomaly is detected after a lockout the burner does 8.8.10 Limitations in the control of the heat request not start. thermostat (HT)  If the anomaly is detected after a shutdown test the burner The condition required for reading the heat request is that the re- does not start.
  • Page 28: 8.10 Programming Menu

    Start-up, calibration and operation of the burner 8.10 Programming menu GENERAL If the number of pressures on the reset push-button exceeds the maximum allowable, the value in memory will remain the maxi- The programming menu can be accessed using the reset push- mum one.
  • Page 29: 8.10.1 Shutdown Test

    Start-up, calibration and operation of the burner  Press reset push-button for 20 sec.  t < 25 sec. 8.10.1 Shutdown test  GREEN led blinking 3 times. Sequence for shutdown test programming  Release the reset push-button.  Programming allowed in OPERATING mode and in STAND- ...
  • Page 30: 8.11 Lock-Out Types

    Start-up, calibration and operation of the burner 8.11 Lock-out types The control box display causes of malfunctioning any time that lock-out occure, identified by the reset push-button color. The se- quence of led pulses in the reset push-button issued by the con- trol box identifies the possible types of malfunction, which are listed in the table below.
  • Page 31: Maintenance

    Check to make sure that no dust has accumulated inside the fan lines suitable for bio fuel use. or on its blades, as this condition will cause a reduction in the air Please contact Riello for further information. flow rate and provoke polluting combustion. Photoresistance Fuel tank Clean the photoresistance.
  • Page 32 Maintenance Boiler Clean the boiler as indicated in the appliance accompanying in- structions in order to maintain all the original combustion charac- teristics intact, especially the flue gas temperature and combustion chamber pressure. Combustion In case the combustion values found at the beginning of the inter- vention do not respect the standards in force or, in any case, do not correspond to a proper combustion, contact the Technical As- sistant and have him carry out the necessary adjustments.
  • Page 33: Faults / Solutions

    Faults / Solutions Faults / Solutions Here below you can find some causes and the possible solutions When lock out lamp lights the burner will attempt to light only after for some problems that could cause a failure to start or incorrect pushing the reset push-button.
  • Page 36 RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.riello.it http:// www.riello.com Subject to modifications...

This manual is also suitable for:

744ld2x20034605