Pump Pressure - Riello Gulliver RG1 Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

B
Fig. 11
Remove nozzle-holder assembly (1) after loos-
ing screws (2) and nut (3), remove the small ca-
b l e s ( 4 ) f r o m t h e c o n t r o l b o x a n d t h e
photoresistance (6).
Withdraw the small cables (4) from the elec-
trodes, remove the diffuser disc-holder assem-
bly (10) from the nozzle-holder assembly (1)
after loosing screw (3, fig. 12).
Screw the nozzle (11) correctly and tighten
it as shown in figure.
ATTENTION
During the reassembly of the nozzle-holder
assembly screw the nut (3) as shown in the figure
below.
TIGHTEN WITHOUT MOVING
BACKWARDS TO THE END
4.3 SETTING OF DIFFUSER DISC /
ELECTRODES (
see fig. 12)
ATTENTION
Loosen screw (3) to set the dif-
fuser disc-holder assembly (1)
and loosen screw (4) to set the
electrodes assembly (2).
To have access to the electrodes
carry out operation as described in
chapter "4.2 RECOMMENDED
NOZZLES" (page 6).

4.4 PUMP PRESSURE

The pump leaves the factory set at 12 bar.
To change it act on pump pressure adjust screw (4, fig. 5, page 4).
D5684
3
Fig. 12
B
Fig. 11
0
4.5
– 0.5 mm
2
4
3
D5028
7
GB
S7206
MEASURES
WARNING
MUST BE RESPECTED
±
2.5
0.2 mm
0
1
3
+ 0.5 mm
20024093