Do not apply excessive force to the power cord.
The electrical installation should be carried out by the technician as instructed by the local and
national regulations, codes and standards. This manual should be followed.
The diameter of the power cord should meet the recommendations in Table 9. Always replace a
damaged power cord with the equivalent specified cord.
Always ensure the unit is correctly earthed and the earth wire is connected to the dedicated device
of the building by the technician. Select the air switch coupled with the leakage current protection
switch as per Table 9 recommendations to meet capacity, magnetic and thermal tripping functions
in the event of a short circuit and overload.
2.3.
Earthing Requirements
The air conditioner is classified a Class I appliance and must be earthed.
The yellow-green wire is the earth line and cannot be: used for any other purpose, cut off, or fixed
by a self-tapping screw. Incorrect installation cause electrical hazard including electric shock or
death.
A suitable earth terminal should be provided, and the earth wire must not be connected to any of
the following places:
1.
Potable water pipes;
2.
Gas pipes;
3.
Sewage pipes;
4. Telecommunications earth wires.
13 23 50
|
lennoxaus.com.au
LENNOX MULTI SPLIT INVERTER
Slim Line Ducted Indoor Unit
7