be fixed as close as possible to the side of the unit.
7.
The drain pipe is not supplied with the unit and should be provided by others. Slide the end of the
PVC pipe over the drain outlet and secure with a hose clamp. Never connect the drain pipe to the
outlet by adhesive. (See Figure 15).
8. When a single drain pipe is used for multiple devices, the common section of the pipe should be
100mm lower than the drain hole of each device and should be sized appropriately for the total
water flow.
9.
Condensate drains located in the air-conditioned space should be insulated to prevent water
damage.
Correct - With a minimum degree of slope 1/100
Figure 14: Correct Condensate Drain Pipe Design and Installation
Figure 15: Correct Condensate Drain Pipe Design and Installation
3.10. Precautions when Installing a Lift Pipe
A lift pipe should be used in situations where a sufficient fall cannot be provided for a standard
condensate drain connection.
The installation height of the lift pipe should be less than 850mm. It is recommended to set an
inclination angle 1° - 2° for the lift pipe toward the drainage direction. If the lift pipe and the unit
form a right angle, the height of the lift pipe must be less than 800mm.
13 23 50
|
lennoxaus.com.au
LENNOX MULTI SPLIT INVERTER
Slim Line Ducted Indoor Unit
Incorrect
17