3.15. Wiring of the Power Cable (Single Phase)
CAUTION
The power supply for each indoor unit must be uniform.
1.
Remove the cover of the electric box of the indoor unit.
2.
Insert the power cable through the rubber ring.
3.
Connect the wiring (communication) through the piping hole of the chassis and upward through
the bottom of the appliance
4. Connect the brown wire to the Terminal board "3"; black wire (the communication wire) to the
Terminal board "2"; blue wire to the Terminal board "N(1)",and connect the earthing wire to the screw
terminal on the electric box. Clamp them with the corresponding wire clamp packed in the chassis.
5.
Fix the power cable tightly with the binding wire.
LNMT100V4
22
Figure 21 - Wiring of the Power Cable - LNMT100V4