18.1.9. QUIET ALARM

One or more smoke detectors, via EBLWin programmed for Quiet alarm, have passed the fire alarm level. Quiet alarm is used for
activating outputs based on smoke detected by a smoke detector without activating fire alarm in the system.
INDICATIONS AND ACTIONS:
Detector LEDs are turned on (i.e. also a connected ext. LED). The buzzer sounds (0.8 / 5 sec.) and there is a Quiet alarm presenta-
tion (including a title "Quiet alarm") in the display:
Quiet alarm
123-45
Zone
Address
SMOKE
User definable alarm text for 123-45
Menu
Programmable outputs for quiet alarm, i.e. any output with a control expression containing the trigger conditions "Quiet Alarm Zone"
or "Quiet Alarm Zone Address".
Quiet Alarms are automatically reset; see section
on page 53.
19.10. QUIET ALARM RESET
A detector programmed for Quiet alarm can never generate a real fire alarm.
48