Orion ONLINE RTX1 User Manual page 26

Rack/tower online ups
Table of Contents

Advertisement

12: Battery total AH setting
Interface
13: Maximum charger current setting
Interface
14: Charger boost voltage setting
Interface
15: Charger float voltage setting
Interface
Setting
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
Setting
Parameter 2: Set up the charger maximum current.
For low voltage model with 24/36/48VDC
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 2A)
For high voltage model with 24/36/48VDC
1/2/4/6/8/10/12: setting the charger maximum current
1/2/4/6/8/10/12 in Ampere. (Default: 2A)
For low voltage and high voltage model with 72/96VDC
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 2A)
Note: Please set the appropriate charger current based on
battery capacity used. The recommended charging current
is 0.1C~0.3C of battery capacity as following table for
reference.
Battery capacity(AH)
7~20
20~40
40~60
60~80
80~100
100~150
Setting
Parameter 2: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
Setting
Parameter 2: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
24
Total charging current (A)
2
4
6
8
10
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dc1000rtx1Dc1500rtx1Dc2000rtx1Dc3000rtx1Dc3000rtx1hv

Table of Contents