ONLINE RTX1
User Manual
UNITY PF
1K/1.5K/2K/3K
Rack/Tower Online UPS
Uninterruptible Power Supply System
Version: 1.1
www.orionpowersystems.com

Advertisement

Table of Contents
loading

Summary of Contents for Orion ONLINE RTX1

  • Page 1 ONLINE RTX1 User Manual UNITY PF 1K/1.5K/2K/3K Rack/Tower Online UPS Uninterruptible Power Supply System Version: 1.1 www.orionpowersystems.com...
  • Page 2: Table Of Contents

    Table of Contents 1. Important Safety Warning ................1 1-1. Transportation....................1 1-2. Preparation ......................1 1-3. Installation ......................1 1-4. Operation......................2 1-5. Maintenance, service and faults ................3 2. Installation and setup ..................6 2-1. Rear panel view....................6 2-2.
  • Page 3: Important Safety Warning

    Avertisseme 1. Important Safety Warning - nt de sécurité important Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
  • Page 4: Operation

    accessible and close to the UPS system. Connectez le système UPS uniquement à une prise antichoc mise à la terre qui doit être facilement accessible et proche du système UPS. ⚫ Please use only VDE-tested, CE-marked (or UL-marked for 100/110/115/120/127 VAC models) mains cable (e.g.
  • Page 5: Maintenance, Service And Faults

    1-5. Maintenance, service and faults - Maintenance, service et défauts ⚫ The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Le système UPS fonctionne avec des tensions dangereuses. Les réparations ne peuvent être effectuées que par un personnel de maintenance qualifié. ⚫...
  • Page 6 Remove battery grounds during installation and maintenance to reduce likelihood of shock. Remove the connection from ground if any part of the battery is determined to be grounded. Les batteries peuvent provoquer un choc électrique et avoir un courant de court- circuit élevé.
  • Page 7 ⚫ For UPS with internally mounted battery Pour UPS avec batterie montée en interne Instructions shall carry sufficient information to enable the replacement of the battery with a suitable manufacturer and catalogue number. Les instructions doivent contenir suffisamment d'informations pour permettre le remplacement de la batterie par un fabricant et un numéro de catalogue appropriés.
  • Page 8: Installation And Setup

    2. Installation and setup - Installation et configuration NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. REMARQUE: Avant l'installation, veuillez inspecter l'appareil. Assurez-vous que rien à l'intérieur de l'emballage n'est endommagé.
  • Page 9: Operating Principle

    2-2. Operating principle The operating principle of the UPS is shown as below Output Input Dynamic Bypass Rectifier EMI/RFI Inverter Filters /PFC DC-to-DC Converter Battery Battery Charger The UPS is composed of mains input, EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output.
  • Page 10 Tower Installation Step 1 Step 2 Step 3...
  • Page 11: Setup The Ups

    2-4. Setup the UPS - Configurer l'onduleur Before installing the UPS, please read below to select proper location to install UPS. Avant d'installer l'onduleur, veuillez lire ci-dessous pour sélectionner l'emplacement approprié pour installer l'onduleur. 1. UPS should be placed on the flat and clean surface. Place it in an area away from vibration, dust, humidity, high temperature, flammable liquids, gases, corrosive and conductive contaminants.
  • Page 12 4. Place UPS - Placez UPS: It’s equipped with fan for cooling. Therefore, place the UPS in a well-ventilated area. It’s required to maintain minimum clearance of 100mm in the front of the UPS and 300mm in the back and two sides of the UPS for heat dissipation and easy-maintenance. Il est équipé...
  • Page 13 Step 1: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. ⚫ For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package. ⚫ For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA 5-15P for 1K and 1.5K models, NEMA 5-20P for 2K model and NEMA L5-30P for 3K model.
  • Page 14 Step 5: Network connection Network/Fax/Phone surge port Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line cable. Step 6: Disable and enable EPO function This UPS is equipped with EPO function.
  • Page 15: Battery Replacement

    2-5. Battery Replacement NOTICE: This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads.(hot-swappable battery design) Replacement is a safe procedure, isolated from electrical hazards. CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. PRUDENCE!! Tenez compte de tous les avertissements, avertissements et notes avant de remplacer les piles.
  • Page 16 Step 4 Step 5 Step 6 Remove the top cover of After replacing the Install battery cover plate. battery box and replace the batteries, put the battery inside batteries. box back to original location and re-connect the battery wires. Step 7 Put the front panel back on the unit.
  • Page 17: Battery Kit Assembly (Option)

    2-6 Battery Kit Assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it. battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below drawing.
  • Page 18 battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below drawing. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells as below drawing. below drawing.
  • Page 19 6-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below drawing. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as in one side of plastic shells. below drawing.
  • Page 20: Operations

    3. Operations 3-1. Button operation Button Function ➢ Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. ➢ Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 3 seconds to disable or enable the alarm ON/Mute system.
  • Page 21 Function Display Backup time information Indicates the estimated backup time. H: hours, M: minute, S: second. Configuration and fault information Indicates the configuration items, and the configuration items are listed in details in section 3-5. Indicates the warning and fault codes, and the codes are listed in details in section 3-7 and 3-8.
  • Page 22: Audible Alarm

    3-3. Audible Alarm Battery Mode Sounding every 5 seconds Low Battery Sounding every 2 seconds Overload Sounding every second Fault Continuously sounding Bypass Mode Sounding every 10 seconds 3-4. LCD display wordings index Abbreviation Display content Meaning Enable Disable Escape High loss Low loss Active open...
  • Page 23 01: Output voltage setting ⚫ Interface Setting Parameter 2: Output voltage For 200/208/220/230/240 VAC models, you may choose the following output voltage: 200: presents output voltage is 200Vac 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac (Default) 240: presents output voltage is 240Vac For 100/110/115/120/127 VAC models, you may choose the...
  • Page 24 05: ECO voltage range setting ⚫ Interface Setting Parameter 2: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to +24V of the nominal voltage.
  • Page 25 08: Bypass frequency range setting ⚫ Interface Setting Parameter 2: Set the acceptable high frequency point and acceptable low frequency point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high frequency point For 50Hz output frequency models: 51-55Hz: setting the frequency high loss point from 51Hz to 55HZ(Default: 53.0Hz) For 60Hz output frequency models:...
  • Page 26 12: Battery total AH setting ⚫ Interface Setting Parameter 2: Set up the battery total AH of the UPS. 7-999: setting the battery total capacity from 7-999 in AH. Please set the correct battery total capacity if external battery bank is connected. 13: Maximum charger current setting ⚫...
  • Page 27 16: EPO logic setting ⚫ Interface Setting Parameter 2: Set up the EPO function control logic. AO: Active Open (Default). When AO is selected as EPO logic, it will activate EPO function with Pin 1 and Pin 2 in open status. AC: Active Close.
  • Page 28: Operating Mode Description

    00: Exit setting ⚫ Interface Setting Exit the setting mode. 3-6. Operating Mode Description Operating mode Description LCD display Online mode When the input voltage is within acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at online mode.
  • Page 29: Faults Reference Code

    3-7. Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail Battery voltage too high Bus over Battery voltage too low Bus under Charger output short Inverter soft start fail Over temperature Inverter voltage high Overload Inverter voltage Low Charger failure...
  • Page 30: Troubleshooting

    4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy Check if input power cord No indication and alarm even The AC input power is not firmly connected to the though the mains is normal.
  • Page 31: Storage And Maintenance

    Symptom Possible cause Remedy Fault code is shown as 14 and the The UPS shut down Check output wiring and if icon is lighting on LCD automatically because connected devices are in display. Alarm is continuously short circuit occurs on the short circuit status.
  • Page 32: Specifications And Runtime Charts

    6. Specifications * Derate capacity to 80% of capacity when the output voltage is adjusted to 100VAC, 200VAC or 208VAC. ** Product specifications are subject to change without further notice. MODEL DC1000RTX1 DC1500RTX1 DC2000RTX1 DC3000RTX1 DC3000RTX1HV CAPACITY* 1000VA/1000W 1500VA/1500W 2000VA/2000W 3000VA / 3000W 3000VA / 3000W INPUT...
  • Page 33 + 2 EBM 1364 + 3 EBM 2019 + 4 EBM 2700 DC3000RTX1 + 1 EBM 1206 + 2 EBM 2187 + 3 EBM 3224 1110 + 4 EBM 4302 1490 Call Orion Power Systems at 877-385-1654 for long runtime applications...
  • Page 34 Orion Power Systems Service and Technical Support If you have any problems or questions with the UPS, call your local distributor or Orion Power Systems technical support at the following telephone number: In the United States: 1-877-385-1654 Please have the following information ready when you call:...