Daikin HUBBARD HCU2040PXB1 Installation, Commissioning And Maintenance Manual page 30

Hermetic r744 condensing units
Table of Contents

Advertisement

8. EXPOSURE CONTROLS / PERSONAL PROTECTION
ENGINEERING CONTROLS:
Use local exhaust system, if necessary, to keep the concentration of carbon dioxide below all applicable exposure limits.
Under certain conditions, general exhaust ventilation may be acceptable to keep carbon dioxide below the exposure limit
PERSONAL PROTECTIVE EQUIPMENT
SKIN PROTECTION:
Wear insulated neoprene gloves and safety shoes for handling cylinders. Select PPE in accordance with OSHA 29
CFR 1910.132 and 1910.133
EYE PROTECTION:
For normal conditions, wear safety glasses. Where there is reasonable probability of liquid contact, wear chemical
safety goggles.
RESPIRATORY PROTECTION:
None generally required for adequately ventilated work situations. For accidental release or non-ventilated
situations, or release into confined space, where the concentration may be above the PEL, use a self-contained
NIOSH approved breathing apparatus or supplied air respirator. For escape: use the former or a NIOSH approved
gas mask with organic vapor canister.
EXPOSURE GUIDELINES
INGREDIENT NAME
Carbon Dioxide
OTHER EXPOSURE LIMITS FOR POTENTIAL DECOMPOSITION PRODUCTS:
IDLH = 40,000ppm
9. PHYSICAL AND CHEMICAL PROPERTIES
APPEARANCE:
PHYSICAL STATE:
MOLECULAR WEIGHT:
CHEMICAL FORMULA:
ODOR:
SPECIFIC GRAVITY (water = 1.0):
SOLUBILITY IN WATER
pH:
LIQUID DENSITY:
SUBLIMATION POINT (at 1 atm):
VAPOR PRESSURE:
VAPOR DENSITY (air = 1.0):
EVAPORATION RATE:
% VOLATILES:
ODOR THRESHOLD:
FLAMMABILITY:
LEL/UEL:
PARTITIION COEFF(n-octanol/water) Not available
AUTO IGNITION TEMP:
____________________________________________________________________________________________________________
MSDS: R-744
Current Issue Date: May 2015
Copyright HPL March 2021
ACGIH TLV
5000 ppm TWA (8hr)
Colorless liquid
Can be present as a liquid or a gas
44.01
CO2
Slight pungent odor
1.22 @ 19.4˚F (-7˚C)
): 0.90
(vol/vol at 68 F
3.7 (for carbonic acid)
47.6 lb/cu.ft. (762 kg/cu.meter) (saturated at 21.1C (70F) at 1 atm
-78.5C (-109.3F)
838 psig @ 70F
1.52 @ 70˚F (21.˚1C)
High
100
Not applicable
Nonflammable
None/None
Not applicable
OSHA PEL
5000 ppm TWA (8hr)
Page 30 of 169
R-744
OTHER LIMIT
None
Page 6 of 6