Alarms; Alarm Management; Compressor Alarms - Daikin HUBBARD HCU2040PXB1 Installation, Commissioning And Maintenance Manual

Hermetic r744 condensing units
Table of Contents

Advertisement

pRack PR300T can manage both alarms relating to the status of the digital
inputs and to operation of the system. For each alarm, the following are
controlled:
The actions on the devices, if necessary
The output relays (one global and two with diff erent priorities, if
confi gured)
The red LED on the terminal and the buzzer, where present
The type of acknowledgement (automatic, manual, semiautomatic)
Any activation delay
The complete list of alarms, with the related information as described
above, is available in Alarm table.

8.1 Alarm management

All alarms feature the following behaviour:
When an alarm is activated, the red LED fl ashes and the buzzer is
activated (where present); the output relays corresponding to the
global alarm and to any alarms with priority are activated (if confi gured)
Pressing the
(Alarm) button, the red LED stays on steady, the buzzer
is muted and the alarm screen is shown
If there is more than one active alarm, these can be scrolled using
(Up)
(Down). This condition is signalled by an arrow at the bottom
right of the screen
Pressing the
(Alarm) button again for at least 3 seconds
acknowledges the alarms manually, and these are cleared from the
display unless others are active (they are saved in the log)
8.1.1
Priority
For certain alarms, the alarm output relay can be set with two types of priority:
R1: serious alarm
R2: normal alarm
The corresponding relays, once confi gured, are activated when an alarm
with the corresponding priority occurs. For the other alarms, the priority
is fi xed and is associated by default with one of the two relays.
8.1.2
Acknowledgement
The

alarms

can
have
manual,
acknowledgement:
Manual: the alarm is acknowledged by pressing the
button twice, the fi rst time displays the corresponding alarm screen
and mutes the buzzer, the second (extended, for at least 3 seconds)
cancels the alarm (which is saved in the log). If the alarm is still active,
acknowledgement has no eff ect and the signal is shown again.
Automatic: when the alarm condition ceases, the alarm is automatically
reset, the LED comes on steady and the corresponding screen remains
displayed until the
(Alarm) button is pressed and held; the alarm is
saved in the log.
Semiautomatic: acknowledgement is automatic, until a maximum
number of activations in set time. If the number reaches the maximum
set, acknowledgement becomes manual.
For manual acknowledgement, the functions associated with the alarm
are not reactivated until acknowledgement has been completed, while
for automatic acknowledgement they're reactivated as soon as the alarm
condition ceases.
8.1.3
Log
The alarm log can be accessed:
from branch G.a of the main menu
by pressing the
(Alarm) button and then
no active alarms
by pressing
(Enter) after having scrolled all the alarms.
The alarm log screens show:
1.
Order of activation (no. 01 is the oldest alarm)
2.
Hour and date the alarm was activated
3.
Short description
4.
Main values recorded at the moment the alarm was activated
(suction pressure and condensing pressure).
Copyright HPL March 2021
8. ALARMS
automatic
or
semiautomatic
(Alarm)
(Enter) when there are
Note: A maximum of 50 alarms can be logged; after this limit any
new events overwrite the oldest ones, which are therefore deleted.

8.2 Compressor alarms

The number of alarms for each compressor can be set during the
confi guration phase using the Wizard or subsequently from branch C.a.e/
C.b.e of the main menu. The number of alarms is the same for all the
compressors on the same line.
Alarms
Number of alarms
for each compressor:
Note: The maximum number of alarms that can be confi gured for
each compressor depends not only on the type of compressor, but
also on the size of pRack and the number of compressors fi tted.
After having selected the number of alarms (maximum 4), the settings
can be confi gured for each alarm, choosing a description from the
options shown in the table, the output relay, the type of reset, delay
and priority. The eff ect of the alarm on the devices is set and involves
stopping the compressor, except for the oil warning.
Possible descriptions for compressor alarms
Reciprocating or scroll
Generic
Overload
High pressure
Low pressure
Oil
An example of a screen for selecting the description of the alarm is shown
in the fi gure:
Alarms
Alarm 1 description:
Generic:
Overload:
High pressure:
Low pressure:
Oil:
After having selected the 'generic' description, no other description can
be selected. In general, the descriptions are divided in:
overload,
oil,
high pressure
low pressure.
After a description has been selected for a certain group, descriptions
from a diff erent group can not be selected for that alarm. For example,
generic only, or overload + oil, or rotation only or overload + high
pressure., etc. can be selected. Each alarm will have one alarm screen,
which will show all the descriptions associated to that alarm.
Starting from version 3.3.0, the main alarms relating to the compressors
have been grouped together; specifi cally, the alarms can be confi gured
in the path: C.Compressors
show which compressors (only those confi gured) will be shutdown
(and which not) when a specifi c alarm is activated (generic alarm, high
pressure..); for example, with 3 compressors and the fi rst 2 with alarms,
the following will occur:
83
Page 132 of 169
Cae01
3
Fig. 8.a
Tab. 8.a
Cae02
Fig. 8.b
d.Alarms
Cae01 (Fig.8.a). The screens
P4367 Rev 01
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
ENG

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hubbard hcu-pxb1

Table of Contents