[5d] External static pressure & High-ceiling adjustment
<Compact Slim Duct type>
External static pressure
Set data
0000
10 Pa
Standard (Factory default)
0001
20 Pa
High static pressure 1
0003
30 Pa
High static pressure 2
<4-way Cassette, 2-way Cassette, 1-way Cassette SH Type>
High-ceiling adjustment
Set data
0000
Standard (Factory default)
0001
High ceiling 1
0003
High ceiling 3
<Compact 4-way Cassette>
Set data
High-ceiling adjustment
0000
Standard (Factory default)
0001
High ceiling 1 (UP015 only)
0003
High ceiling 3 (UP015 only)
<Under Ceiling type>
High-ceiling adjustment
Set data
0000
Standard (Factory default)
0003
High ceiling 1
<Concealed Duct Type>
External static pressure
Set data
0000
40 Pa
UP024 to 030 (Factory default)
0001
30 Pa
UP007 to 018 (Factory default)
0002
65 Pa
0003
50 Pa
UP036 to 056 (Factory default)
0004
80 Pa
0005
100 Pa
0006
120 Pa
<Slim Duct type>
External static pressure
Set data
0000
10 Pa
Standard (Factory default)
0001
20 Pa
High static pressure 1
0003
35 Pa
High static pressure 2
0006
50 Pa
High static pressure 3
<Concealed Duct High Static Pressure Type (6 HP or less)>
External static pressure
Set data
0000
100 Pa
Standard (Factory default)
0001
50 Pa
0002
75 Pa
0003
150 Pa
0004
125 Pa
0005
175 Pa
0006
200 Pa
<Concealed Duct High Static Pressure Type (8, 10 HP)>
External static pressure
Set data
0000
150 Pa
Standard (Factory default)
0001
50 Pa
0002
83 Pa
0003
217 Pa
0004
117 Pa
0005
183 Pa
0006
250 Pa