Check codes Detected by Central Control Device
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
C05
C06
C12
Differs according to
nature of alarm-causing
trouble
P30
(L20 displayed.)
Location
Description
System status
of
detection
Central
Central control
Continued
control
device
operation
device
transmission
trouble
Central
Central control
Continued
control
device reception
operation
device
trouble
General-
Batch alarm
Continued
purpose
for general-
operation
device
purpose
I/F
device
control interface
Central
Group control
Continued
control
follower unit
operation
device
trouble
Duplicated
Continued
central control
operation
address
- 197 -
Check code detection
Check items (locations)
condition(s)
Central control device is
• Check for failure in central
unable to transmit signal.
control device.
• Check for failure in central
control communication line.
• Check termination
resistance setting.
Central control device is
• Check for failure in central
control device.
unable to receive signal.
• Check for failure in central
control communication line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check failure in P.C.
boards of devices at other
end of central control
communication line.
Trouble signal is input to
• Check trouble input.
control interface for general-
purpose devices.
Trouble occurs in follower
• Check check code of unit
unit under group control.
that has generated alarm.
([P30] is displayed on central
control remote controller.)
There is duplication in
• Check address settings.
central control addresses.