No.
Part
WARNING
5
Reactor
assembly
Wear a pair of gloves.
(16-24HP)
Otherwise, you will risk an injury involving a replacement
part or some other object.
1. Detachment
1) Stop the air conditioner operation, and turn off the
circuit breaker.
2) Following to works 1) to 5) in 1 of No.1 Cabinet,
remove the cabinets.
3) Remove the screws for the fixed plate of reactor box.
(M5 × 10, 4 pcs)
4) Remove the screws for the reactor box, and draw the
reactor box toward you.
(M5 × 10, 2 pcs, Rear side is hooked)
5) Remove the reactor cover.
(M4 × 8, 6 pcs)
6) Remove the reactor.
(M4 × 8, 4 pcs)
2. Attachment
Carry out installation by following reverse procedure in the
detachment 1) to 6).
Hook the hooks on each cabinet securely into the square
holes in the supports.
[When attaching two reactors for 22, 24 HP]
Be sure to wire the round type terminal leads to the
specified reactors.
Reactor 1: Wire the round type terminal lead without the
Reactor 2: Wire the round type terminal lead with the black
Work procedure
black tape to the reactor 1.
tape to the reactor 2.
- 282 -
Remarks
3) Fixed plate of reactor box
4) Screw for reactor box
5) Screws for
reactor cover
6) Screw for reactor box