Toshiba MMY-MUP0801HT8P-TR Service Manual page 104

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

6-6-3-7. Trouble/Operation Output
Header outdoor unit
Outdoor unit
interface PCB
Operation
In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation
in the line.
Trouble output: Trouble indication signal is output if trouble occurs in at least one indoor/outdoor unit in the line.
Note 1: Output Relay (K1, K2) Contact Specifications
• Output terminals (OUTPUT1, 2) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1 and K2, insert a surge killer CR (for an AC power
supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
C1
Attached connection cable 1 (4wires)
CN511
Connector on interface side (green)
K1, K2
Relays
L1
Trouble indication Lamp
L2
Operation indication Lamp
OUTPUT1
Trouble output
OUTPUT2
Operation output
PJ20
Connector on optional P.C.board side
PS
Power supply unit
TB1
Terminal block
The optional P.C. board should be connected to the header outdoor unit (U1).
Optional PCB
TB1
C1
K1
CN511
PJ20
K2
Locally procured
(See "NOTE")
L1
1
OUTPUT1
2
L2
3
OUTPUT2
4
5
OUTPUT3
Shield
6
wire
- 104 -