Compressor P.c. Board (Mcc-1729) Replacement Procedure - Toshiba MMY-MUP0801HT8P-TR Service Manual

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

(11) "L10 : Outdoor capacity not set" check code is displayed on the 7-segment display.
Perform a model change by the following flow.
SW01 15
SW02 2
SW03 1
(7seg. "re_C1")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_C1"
Setup complete
Arrangement of a switch
(12) Set SW01 :1, SW02 : 1, SW03 : 1. Check the operation.

13-1-4. Compressor P.C. Board (MCC-1729) Replacement Procedure

43T6W892:
Target model
43T6W893:
This board is commonly installed in different models. Set the DIP switch (SW800) setting of the service board
to the switch setting before replacement.
Included item:
MCC-1729 : 1pcs
SW01 15
SW02 2
SW03 2
(7seg. "re_C2")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_C2"
Setup complete
MMY-MUP0801*/1001*/1201*/1401*
MMY-MUP2201*/2401*
MMY-MUP1601*/1801*/2001*
Spacer : 4pcs
Bush : 2pcs
- 293 -
SW01 15
SW02 2
SW03 4
(7seg. "re_F1")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_F1"
Setup complete
Collar : 2pcs
SW01 15
SW02 2
SW03 5
(7seg. "re_F2")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_F2"
Setup complete
Please perform the model
change by manual operation.
(Refer to "Outdoor DN setup" of
a service manual.)