Fujitsu AUXG22KVLA Design & Technical Manual page 166

Hide thumbs Also See for AUXG22KVLA:
Table of Contents

Advertisement

Switch button
S134
S133
S132
S131
S130
 Function setting table
No.
Setting item
Level 1
Low noise
1
mode setting
Level 2
Level 1
Level 2
Peak cut mode
2
setting
Level 3
Level 4
Sign "○": Lights off, "●": Lights on
No.
Setting item
1
Low noise mode setting
2
Peak cut mode setting
8-1. Outdoor unit
MODE
Switches between "Local setting" and "Error code display".
Switches between the individual "Local settings" and the "Error code
SELECT
displays".
Switches between the individual "Local settings" and the "Error code
ENTER
displays".
EXIT
Returns to "Operation status display".
PUMP DOWN
Starts the pump down operation.
POWER
ERROR
MODE
Blink
(9 times)
By using the "Low noise mode", the limit of the noise level will be set to decrease
the noise level. The mode comes in 2 levels which can be set accordingly.
To turn on the mode, use the external input terminal (P580).
• By using this mode, the cooling/heating performance may decrease.
• Depending on the operating condition, the noise level may not decrease even if
the Low noise mode is on.
The capacity limit can be selected when operating with the "Peak cut mode." The
operation selection can be done by external input terminal (PA580).
The lower the level, the more the effect of energy saving, but the cooling/heating
performance decreases.
Function or operation method
LED display
PUMP
LOW NOISE
DOWN
(L1)
(L2)
(L3)
Content
- 158 -
Factory
PEAK CUT
setting
(L4)
(L5)
(L6)
8. Function settings