¢ External output
With using external output function, some status signals are transmitted to the control PCB, and the
related LED lamp indicates the status of this product.
 Error status output
Signal on air conditioner error status is generated when a malfunction occurs.
• Circuit diagram example
Outdoor unit
control PCB
Connector
12 V
1
On/
Off
2
1
On/
Off
2
Error status
Output signal
• Optional part
Part name
External connect kit
6-2. Outdoor unit
Connected unit (Locally purchased)
Example:
Relay unit
10m*
Signal
Error
Normal
On
Off
Model name
UTY-XWZXZ3
• Output voltage (Vcc): DC 12 V
50 mA or less
• *: Make the distance from the
Example: Fan
PCB to the connected unit with-
in 10 m.
- 137 -
Exterior
External output wire
6. External input and output