Fujitsu ARXG22KMLB Design & Technical Manual

Fujitsu ARXG22KMLB Design & Technical Manual

Hide thumbs Also See for ARXG22KMLB:
Table of Contents

Advertisement

AIR CONDITIONER
4-unit multi-split type,
5-unit multi-split type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07KGTB
ASYG09KGTB
ASYG12KGTB
ASYG14KGTB
ASYG07KETA-B
ASYG09KETA-B
ASYG12KETA-B
ASYG14KETA-B
AUXG07KVLA
ARXG07KSLAP
AUXG09KVLA
ARXG09KSLAP
AUXG12KVLA
ARXG12KSLAP
AUXG14KVLA
ARXG14KSLAP
AUXG18KVLA
ARXG18KSLAP
AUXG22KVLA
ASYG18KMTB
ASYG22KMTB
ASYG24KMTB
ABYG18KRTA
AGYG09KVCA
ABYG22KRTA
AGYG12KVCA
AGYG14KVCA
ARXG07KLLAP
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
ARXG18KLLAP
ASYG07KMTB
ASYG07KMCC
ASYG09KMTB
ASYG09KMCC
ASYG12KMTB
ASYG12KMCC
ASYG14KMTB
ASYG14KMCC
OUTDOOR
ARXG22KMLB
ASYG07KETA
ASYG09KETA
ASYG12KETA
ASYG14KETA
AOYG30KBTA4
AOYG36KBTA5
DR_MU025EF_03
2021.04.19

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ARXG22KMLB

  • Page 1 AIR CONDITIONER 4-unit multi-split type, 5-unit multi-split type DESIGN & TECHNICAL MANUAL INDOOR AUXG07KVLA ARXG07KSLAP ARXG07KLLAP ARXG22KMLB AUXG09KVLA ARXG09KSLAP ARXG09KLLAP AUXG12KVLA ARXG12KSLAP ARXG12KLLAP AUXG14KVLA ARXG14KSLAP ARXG14KLLAP AUXG18KVLA ARXG18KSLAP ARXG18KLLAP AUXG22KVLA ASYG07KGTB ASYG18KMTB ASYG07KMTB ASYG07KMCC ASYG07KETA ASYG09KGTB ASYG22KMTB ASYG09KMTB ASYG09KMCC ASYG09KETA...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Indoor unit connection patterns..................3 2. Specifications....................10 2-1. Compact cassette type ....................10 2-2. Mini duct type.........................12 2-3. Slim duct type ........................14 2-4. Medium static pressure duct type ..................16 2-5. Wall mounted type ......................17 2-6.
  • Page 4 CONTENTS (continued) 7-4. Medium static pressure duct type ................117 7-5. Wall mounted type .......................118 7-6. Ceiling type ........................122 7-7. Floor type........................123 8. Noise level curve..................124 8-1. Compact cassette type ....................124 8-2. Mini duct type.......................127 8-3. Slim duct type ......................130 8-4. Medium static pressure duct type ................133 8-5.
  • Page 5 CONTENTS (continued) 14-8.Wired remote controller (UTY-RLRY) .................279 14-9.Wired remote controller (UTY-RNRYZ*) ..............279 14-10.Simple remote controller (UTY-RSNYM)..............280 15. Accessories ....................281 15-1.Compact cassette type ....................281 15-2.Mini duct type......................282 15-3.Slim duct type ......................284 15-4.Medium static pressure duct type ................285 15-5.Wall mounted type ......................286 15-6.Ceiling type .........................289 15-7.Floor type ........................290 16.
  • Page 6 CONTENTS (continued) Part 2. OUTDOOR UNIT (4 UNITS TYPE) ........303 1. Specifications....................304 2. Dimensions....................306 2-1. Model: AOYG30KBTA4 ....................306 3. Installation space ..................307 3-1. Model: AOYG30KBTA4 ....................307 4. Refrigerant circuit ..................310 4-1. Model: AOYG30KBTA4 ....................310 5. Wiring diagram ..................311 5-1. Model: AOYG30KBTA4 ....................311 6.
  • Page 7 CONTENTS (continued) Part 3. OUTDOOR UNIT (5 UNITS TYPE) ........377 1. Specifications....................378 2. Dimensions....................380 2-1. Model: AOYG36KBTA5 ....................380 3. Installation space ..................381 3-1. Model: AOYG36KBTA5 ....................381 4. Refrigerant circuit ..................384 4-1. Model: AOYG36KBTA5 ....................384 5. Wiring diagram ..................385 5-1. Model: AOYG36KBTA5 ....................385 6.
  • Page 8 CONTENTS (continued) 17-2.Points to remember when installing ................453...
  • Page 9: Part 1. Indoor Unit

    AUXG07KVLA AUXG14KVLA ARXG07KSLAP ARXG14KSLAP AUXG09KVLA AUXG18KVLA ARXG09KSLAP ARXG18KSLAP AUXG12KVLA AUXG22KVLA ARXG12KSLAP SLIM DUCT TYPE: MEDIUM STATIC PRES- SURE DUCT TYPE: ARXG07KLLAP ARXG14KLLAP ARXG22KMLB ARXG09KLLAP ARXG18KLLAP ARXG12KLLAP WALL MOUNTED TYPE: ASYG07KGTB ASYG18KMTB ASYG07KMTB ASYG07KMCC ASYG07KETA(-B) ASYG09KGTB ASYG22KMTB ASYG09KMTB ASYG09KMCC ASYG09KETA(-B) ASYG12KGTB...
  • Page 10: Model Lineup

    1. Model lineup Indoor unit AUXG07KVLA ARXG07KSLAP ARXG07KLLAP ARXG22KMLB AUXG09KVLA ARXG09KSLAP ARXG09KLLAP AUXG12KVLA ARXG12KSLAP ARXG12KLLAP AUXG14KVLA ARXG14KSLAP ARXG14KLLAP AUXG18KVLA ARXG18KSLAP ARXG18KLLAP AUXG22KVLA ASYG07KGTB ASYG18KMTB ASYG07KMTB ASYG07KETA ASYG09KGTB ASYG22KMTB ASYG09KMTB ASYG09KETA ASYG12KGTB ASYG24KMTB ASYG12KMTB ASYG12KETA ASYG14KGTB ASYG14KMTB ASYG14KETA ASYG07KMCC ASYG09KMCC ASYG12KMCC...
  • Page 11: Indoor Unit Connection Patterns

    1-1. Indoor unit connection patterns ¢ 4-unit multi-split type AOYG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — — — — — — —...
  • Page 12 AOYG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — Numbers in column Unit 1 to 4, and Total indicate the indoor unit capacities as follows: - 4 - 1-1.
  • Page 13 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..- 5 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 14 ¢ 5-unit multi-split type AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 15 AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 16 AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 17 AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total Numbers in column Unit 1 to 5 and Total indicate the indoor unit capacities as follows: 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..*: As for the 22 model, wall-mounted type indoor unit is only connectable.
  • Page 18: Specifications

    2. Specifications 2-1. Compact cassette type Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.19 0.22 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 19 Model name AUXG18KVLA AUXG22KVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.30 0.62 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Turbo fan × 1 Motor output HIGH Cooling...
  • Page 20: Mini Duct Type

    2-2. Mini duct type Model name ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.29 0.33 0.38 0.58 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET...
  • Page 21 Model name ARXG18KSLAP Power supply 1Ø 230 V ~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.49 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 50...
  • Page 22: Slim Duct Type

    2-3. Slim duct type Model name ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.33 0.30 0.35 0.51 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 23 Model name ARXG18KLLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.44 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 90 HIGH...
  • Page 24: Medium Static Pressure Duct Type

    2-4. Medium static pressure duct type Model name ARXG22KMLB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.60 HIGH 1,100 Cooling QUIET Airflow rate HIGH 1,100 Heating QUIET Type × Q'ty Sirocco fan ×...
  • Page 25: Wall Mounted Type

    2-5. Wall mounted type Model name ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 26 Model name ASYG18KMTB ASYG22KMTB ASYG24KMTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power 37.5 47.0 61.6 Running current 0.35 0.39 0.44 HIGH 1,060 1,170 Cooling QUIET Airflow rate HIGH 1,020 1,060 1,170 Heating QUIET...
  • Page 27 Model name ASYG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
  • Page 28 Model name ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
  • Page 29 ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA Model name ASYG07KETA-B ASYG09KETA-B ASYG12KETA-B ASYG14KETA-B Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 30: Ceiling Type

    2-6. Ceiling type Model name ABYG18KRTA ABYG22KRTA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.21 0.25 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco × 2 Motor output HIGH Cooling...
  • Page 31: Floor Type

    2-7. Floor type Model name AGYG09KVCA AGYG12KVCA AGYG14KVCA Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.18 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Cross flow fan ×...
  • Page 32: Dimensions

    3. Dimensions 3-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA Unit: mm Grid type grille Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View C View B a: Ceiling openings Cassette grille (Option [Grid type]) 580 to 610 - 24 - 3-1.
  • Page 33  Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) 07 and 09 models 12 or larger models Standard 2,700 High ceiling —...
  • Page 34: Mini Duct Type

    3-2. Mini duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, and ARXG14KSLAP Unit: mm Rear view View A Drain port P 100 × 6 = 600 Top view Side view Front view Bottom view - 26 - 3-2. Mini duct type 3.
  • Page 35 ¢ Model: ARXG18KSLAP Unit: mm Rear view View A Drain port P 100 × 8 = 800 Top view Side view Front view Bottom view - 27 - 3-2. Mini duct type 3. Dimensions...
  • Page 36  Installation space requirement Provide sufficient installation space for product safety. Unit: mm Strong and durable ceiling Indoor unit Left Right side side or more* or more *: 400 or more when drain from drain pipe • When intaking air from back: •...
  • Page 37: Slim Duct Type

    3-3. Slim duct type ¢ Models: ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, and ARXG14KLLAP Unit: mm View A Rear view Drain port 100 x 6 = 600 Side view Top view Front view Bottom view - 29 - 3-3. Slim duct type 3. Dimensions...
  • Page 38 ¢ Model: ARXG18KLLAP Unit: mm Rear view View A Drain port 100 × 8 = 800 Top view Side view Front view Bottom view - 30 - 3-3. Slim duct type 3. Dimensions...
  • Page 39  Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor ...
  • Page 40: Medium Static Pressure Duct Type

    3-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Unit: mm Φ205 Φ3.2 Front view 1,177 Gas pipe Drain port Liquid pipe Φ200 Knockout Drain port for fresh air Φ5 Φ3.2 80 80 P125 × 3 = 375 P125 × 3 = 375 Φ5...
  • Page 41  Maintenance space requirement Unit: mm • Provide a service access for maintenance purposes. Maintenance hole Control box • The service access necessary for fan units and filter maintenance. Maintenance hole Intake panel Control box 1,550 • When using a square duct P174 ×...
  • Page 42: Wall Mounted Type

    3-5. Wall mounted type ¢ Models: ASYG07KGTB, ASYG09KGTB, ASYG12KGTB, and ASYG14KGTB Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 34 - 3-5. Wall mounted type 3. Dimensions...
  • Page 43  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 44 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 36 - 3-5. Wall mounted type 3. Dimensions...
  • Page 45  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more Wall hook bracket 70 or more Outline of the indoor unit 160 or more 117 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 46 ¢ Models: ASYG07KMTB, ASYG09KMTB, ASYG12KMTB, ASYG14KMTB, ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 38 - 3-5. Wall mounted type 3. Dimensions...
  • Page 47  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 48 ¢ Models: ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG14KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, and ASYG14KETA-B Unit: mm (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 40 - 3-5. Wall mounted type 3. Dimensions...
  • Page 49  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 50: Ceiling Type

    3-6. Ceiling type ¢ Models: ABYG18KRTA and ABYG22KRTA Unit: mm 1,080 49 84 125 103 Side view Top view ø100-mm hole Rear view Suspension bolt pitch Dimensions Indoor unit (Top view) (Space required for installation) The length of the bolt here is 30 mm.
  • Page 51 ¢ Installation space requirement Unit: mm Ceiling Indoor unit 30 or more Ceiling 200 or more 0 or more Obstruction Floor Required ceiling height varies according to the ceiling mode setting of function setting No. 20. Ceiling height (m) Ceiling mode Standard High ceiling 18, 22 models...
  • Page 52: Floor Type

    3-7. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA Unit: mm Side view Front view  Installation space 100 or more 80 or more 80 or more 50 or more 150 or below from the floor - 44 - 3-7. Floor type 3.
  • Page 53 PROHIBITED Grating WARNING • The appliance shall be installed, operated and stored in a room with a floor area larger than X Minimum room area Amount of refrigerant charge M (kg) X (m M ≤ 1.22 1.22 < M ≤ 1.23 12.99 1.23 <...
  • Page 54: Wiring Diagrams

    4. Wiring diagrams 4-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA - 46 - 4-1. Compact cassette type 4. Wiring diagrams...
  • Page 55: Mini Duct Type And Slim Duct Type

    4-2. Mini duct type and Slim duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, ARXG14KSLAP, ARXG18KSLAP, ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP WLAN adapter, Converter etc. (Option) - 47 - 4-2. Mini duct type and Slim duct type 4. Wiring diagrams...
  • Page 56: Medium Static Pressure Duct Type

    4-3. Medium static pressure duct type ¢ Model: ARXG22KMLB - 48 - 4-3. Medium static pressure duct type 4. Wiring diagrams...
  • Page 57: Wall Mounted Type

    4-4. Wall mounted type ¢ Models: ASYG07KGTB, ASYG09KGTB, ASYG12KGTB, and ASYG14KGTB - 49 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 58 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB - 50 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 59 ¢ Models: ASYG07KMTB, ASYG09KMTB, ASYG12KMTB, and ASYG14KMTB - 51 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 60 ¢ Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC - 52 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 61 ¢ Models: ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG14KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, and ASYG14KETA-B - 53 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 62: Ceiling Type

    4-5. Ceiling type ¢ Models: ABYG18KRTA and ABYG22KRTA - 54 - 4-5. Ceiling type 4. Wiring diagrams...
  • Page 63: Floor Type

    4-6. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA - 55 - 4-6. Floor type 4. Wiring diagrams...
  • Page 64: Air Velocity And Temperature Distributions

    5. Air velocity and temperature distributions 5-1. Compact cassette type ¢ Models: AUXG07KVLA and AUXG09KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 4 (m) Unit : m/s Side view...
  • Page 65 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions...
  • Page 66 ¢ Model: AUXG12KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: up 0.25 0.25 4 (m)
  • Page 67 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data...
  • Page 68 ¢ Model: AUXG14KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: up 0.25 0.25 4 (m)
  • Page 69 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data...
  • Page 70 ¢ Model: AUXG18KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25 0.25...
  • Page 71 ¢ Model: AUXG22KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
  • Page 72: Mini Duct Type

    5-2. Mini duct type ¢ Model: ARXG07KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 73 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 74 ¢ Model: ARXG09KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 75 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 76 ¢ Model: ARXG12KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 77 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 78 ¢ Model: ARXG14KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 79 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 80 ¢ Model: ARXG18KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 81 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 82: Slim Duct Type

    5-3. Slim duct type ¢ Model: ARXG07KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 83 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 84 ¢ Model: ARXG09KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 85 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 86 ¢ Model: ARXG12KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 87 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 88 ¢ Model: ARXG14KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 89 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 90 ¢ Model: ARXG18KLLAP NOTE: This data is measured installing the Auto louver grille kit (option). Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 91 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center - 83 - 5-3.
  • Page 92: Wall Mounted Type

    5-4. Wall mounted type ¢ Models: ASYG07KGTB, ASYG09KGTB, ASYG07KMTB, ASYG09KMTB, ASYG12KMTB, ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG07KETA-B, ASYG09KETA-B, and ASYG12KETA-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 93 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
  • Page 94 ¢ Models: ASYG12KGTB, ASYG14KGTB, ASYG14KMTB, ASYG14KMCC, ASYG14KETA, and ASYG14KETA-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
  • Page 95: Ceiling Type

    5-5. Ceiling type ¢ Model: ABYG18KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Side view 0.25...
  • Page 96 ¢ Model: ABYG22KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Side view 0.25 Vertical airflow direction louver: Up Horizontal airflow direction louver: Center...
  • Page 97: Floor Type

    5-6. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center UPPER LOWER Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
  • Page 98: Fan Performance

    6. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 6-1. Mini duct type ¢ Model: ARXG07KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Quiet (SP mode 03) Hi (SP mode 03) Normal SP upper limit...
  • Page 99  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 91 - 6-1. Mini duct type 6. Fan performance...
  • Page 100 ¢ Model: ARXG09KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Hi (SP mode 03) Quiet (SP mode 03) SP mode 00 upper limit SP mode 03 lower limit Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 101  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 93 - 6-1. Mini duct type 6. Fan performance...
  • Page 102 ¢ Model: ARXG12KSLAP SP mode 03 upper limit Quiet (SP mode 03) Hi (SP mode 03) Quiet Normal SP (Normal SP) upper limit Quiet SP mode 03 (SP mode 00) lower limit SP mode 00 (Normal SP) upper limit Hi (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 03)
  • Page 103  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 95 - 6-1. Mini duct type 6. Fan performance...
  • Page 104 ¢ Model: ARXG14KSLAP Hi (SP mode 05) SP mode 05 upper limit Quiet (SP mode 00) Nomal SP Quiet upper limit (Nomal SP) Quiet Hi (Normal SP) (SP mode 05) SP mode 05 lower limit SP mode 00 upper limit (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 105  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 97 - 6-1. Mini duct type 6. Fan performance...
  • Page 106 ¢ Model: ARXG18KSLAP SP mode 05 Hi (SP mode 05) upper limit Quiet (SP mode 05) SP mode 05 lower limit Quiet (Normal SP) Quiet (SP mode 00) Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) SP mode 00 upper limit 1,000 1,100...
  • Page 107  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacity 1,000 1,100 Airflow (m - 99 - 6-1. Mini duct type 6. Fan performance...
  • Page 108: Slim Duct Type

    6-2. Slim duct type ¢ Model: ARXG07KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Normal SP upper limit lower limited Quiet (SP mode 00)
  • Page 109  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 101 - 6-2. Slim duct type 6. Fan performance...
  • Page 110 ¢ Model: ARXG09KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) Hi (SP mode00) SP mode 00 upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 09)
  • Page 111  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 103 - 6-2. Slim duct type 6. Fan performance...
  • Page 112 ¢ Model: ARXG12KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Hi (SP mode 00) upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 113  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 105 - 6-2. Slim duct type 6. Fan performance...
  • Page 114 ¢ Model: ARXG14KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) Nomal SP upper limit SP mode 09 lower limit Quiet (Nomal SP) Hi (Normal SP) SP mode 00 upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000...
  • Page 115  Characteristics of air volume and capacity • Cooling Capacity 1,000 Airflow (m • Heating Capacity 1,000 Airflow (m - 107 - 6-2. Slim duct type 6. Fan performance...
  • Page 116 ¢ Model: ARXG18KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) SP mode 00 Hi (Normal SP) upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000 1,100...
  • Page 117  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacitty 1,000 1,100 Airflow (m - 109 - 6-2. Slim duct type 6. Fan performance...
  • Page 118: Medium Static Pressure Duct Type

    6-3. Medium static pressure duct type ¢ Model: ARXG22KMLB (Normal mode) Static pressure (Pa) Fan speed Item — — — — — — — 1200 1100 1000 HIGH — — — — — — — — — — — —...
  • Page 119 ¢ Model: ARXG22KMLB (Static pressure mode 1) Static pressure (Pa) Fan speed Item — — — — — — 1200 1000 HIGH — — — — — — — — — — — — — — — — 1000 —...
  • Page 120 ¢ Model: ARXG22KMLB (Static pressure mode 2) Static pressure (Pa) Fan speed Item — — — — — — 1160 HIGH — — — — — — — — — — — — — — — — 1020 — —...
  • Page 121 ¢ Model: ARXG22KMLB (Static pressure mode 3) Static pressure (Pa) Fan speed Item — — — — — — 1100 HIGH — — — — — — — — — — — — — — — — 1000 — —...
  • Page 122: Airflow

    7. Airflow Conversion factor: • 1 m /h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 7-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling AUXG07KVLA Quiet AUXG09KVLA...
  • Page 123: Mini Duct Type

    7-2. Mini duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KSLAP High Heating Quiet High Cooling Quiet ARXG09KSLAP High Heating Quiet High Cooling Quiet ARXG12KSLAP High Heating Quiet High Cooling Quiet ARXG14KSLAP High Heating Quiet High Cooling Quiet ARXG18KSLAP High...
  • Page 124: Slim Duct Type

    7-3. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KLLAP High Heating Quiet High Cooling Quiet ARXG09KLLAP High Heating Quiet High Cooling Quiet ARXG12KLLAP High Heating Quiet High Cooling Quiet ARXG14KLLAP High Heating Quiet High Cooling Quiet ARXG18KLLAP High...
  • Page 125: Medium Static Pressure Duct Type

    7-4. Medium static pressure duct type Airflow Model Operation mode Fan speed High 1,100 Cooling Quiet ARXG22KMLB High 1,100 Heating Quiet - 117 - 7-4. Medium static pressure duct type 7. Airflow...
  • Page 126: Wall Mounted Type

    7-5. Wall mounted type Airflow Model Operation mode Fan speed High Cooling Quiet ASYG07KGTB High Heating Quiet High Cooling Quiet ASYG09KGTB High Heating Quiet High Cooling Quiet ASYG12KGTB High Heating Quiet High Cooling Quiet ASYG14KGTB High Heating Quiet High Cooling Quiet ASYG18KMTB High...
  • Page 127 Airflow Model Operation mode Fan speed High 1,170 Cooling Quiet ASYG24KMTB High 1,170 Heating Quiet High Cooling Quiet ASYG07KMTB High Heating Quiet High Cooling Quiet ASYG09KMTB High Heating Quiet High Cooling Quiet ASYG12KMTB High Heating Quiet High Cooling Quiet ASYG14KMTB High Heating Quiet...
  • Page 128 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG09KMCC High Heating Quiet High Cooling Quiet ASYG12KMCC High Heating Quiet High Cooling Quiet ASYG14KMCC High Heating Quiet High Cooling ASYG07KETA Quiet High ASYG07KETA-B Heating Quiet High Cooling ASYG09KETA Quiet High ASYG09KETA-B Heating Quiet...
  • Page 129 Airflow Model Operation mode Fan speed High Cooling ASYG14KETA Quiet ASYG14KETA-B High Heating Quiet - 121 - 7-5. Wall mounted type 7. Airflow...
  • Page 130: Ceiling Type

    7-6. Ceiling type Airflow Model Operation mode Fan speed High Cooling Quiet ABYG18KRTA High Heating Quiet High Cooling Quiet ABYG22KRTA High Heating Quiet - 122 - 7-6. Ceiling type 7. Airflow...
  • Page 131: Floor Type

    7-7. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGYG09KVCA High Heating Quiet High Cooling Quiet AGYG12KVCA High Heating Quiet High Cooling Quiet AGYG14KVCA High Heating Quiet - 123 - 7-7. Floor type 7. Airflow...
  • Page 132: Noise Level Curve

    8. Noise level curve 8-1. Compact cassette type ¢ Model: AUXG07KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000...
  • Page 133 ¢ Model: AUXG12KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 134 ¢ Model: AUXG18KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET NC-25 QUIET NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 135: Mini Duct Type

    8-2. Mini duct type ¢ Model: ARXG07KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH NC-35 NC-35 HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 136 ¢ Model: ARXG12KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 137 ¢ Model: ARXG18KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 138: Slim Duct Type

    8-3. Slim duct type ¢ Model: ARXG07KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 139 ¢ Model: ARXG12KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 140 ¢ Model: ARXG18KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 HIGH NC-45 NC-40 NC-40 HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 QUIET NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 141: Medium Static Pressure Duct Type

    8-4. Medium static pressure duct type ¢ Model: ARXG22KMLB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET NC-20 QUIET NC-20 NC-15 NC-15 1,000...
  • Page 142: Wall Mounted Type

    8-5. Wall mounted type ¢ Model: ASYG07KGTB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 143 ¢ Model: ASYG12KGTB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 144 ¢ Model: ASYG18KMTB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 145 ¢ Model: ASYG24KMTB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 146 ¢ Models: ASYG09KMTB, ASYG09KMCC, ASYG09KETA, and ASYG09KETA-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 147 ¢ Models: ASYG14KMTB, ASYG14KMCC, ASYG14KETA, and ASYG14KETA-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 148: Ceiling Type

    8-6. Ceiling type ¢ Model: ABYG18KRTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 149: Floor Type

    8-7. Floor type ¢ Model: AGYG09KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 150 ¢ Model: AGYG14KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 HIGH NC-55 NC-55 HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 151: Sound Level Check Point

    8-8. Sound level check point ¢ Compact cassette type Microphone 1.5 m Microphone - 143 - 8-8. Sound level check point 8. Noise level curve...
  • Page 152 ¢ Mini duct type, Slim duct type, and Medium static pressure duct type Product Measuring duct Measuring duct (Set the static pressure as rating in this area.) Microphone Microphone Front view Side view ¢ Wall mounted type Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above.
  • Page 153 ¢ Floor type Microphone Microphone ● ● Airflow Airflow - 145 - 8-8. Sound level check point 8. Noise level curve...
  • Page 154: Electrical Characteristics

    0.49 ARXG07KLLAP 0.41 0.33 ARXG09KLLAP 0.38 0.30 Slim duct ARXG12KLLAP 0.44 0.35 ARXG14KLLAP 0.64 0.51 ARXG18KLLAP 0.55 0.44 Medium static ARXG22KMLB 1.00 0.60 pressure duct ASYG07KGTB 0.25 0.20 ASYG09KGTB 0.30 0.24 ASYG12KGTB 0.30 0.24 ASYG14KGTB 0.37 0.29 ASYG18KMTB 0.44 0.35 ASYG22KMTB 0.49...
  • Page 155 MCA: Minimum Circuit Ampacity = Maximum operating current (Full load) FLA: Full Load Amperes (Fan motor) - 147 - 9. Electrical characteristics...
  • Page 156: Safety Devices

    ARXG18KSLAP Reset: 105 ±15 °C ARXG07KLLAP Fan motor restart ARXG09KLLAP Slim duct ARXG12KLLAP ARXG14KLLAP ARXG18KLLAP Activate: 135 ±15 °C Fan motor stop Medium static Reset: 115 ±15 °C ARXG22KMLB pressure duct Fan motor restart - 148 - 10. Safety devices...
  • Page 157 Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse ASYG07KGTB Activate: 110 ±15 °C Fan motor speed down Reset: 110 ±15 °C ASYG09KGTB Fan motor speed recover ASYG12KGTB Activate: 125 ±10 °C Fan motor stop Reset: 100 ±10 °C ASYG14KGTB Fan motor restart...
  • Page 158: External Input And Output

    11. External input and output 11-1. Compact cassette type, Mini duct type, Slim duct type, and Medium static pressure duct type Exterior of the indoor unit PCB and the component location differ by the type of the indoor unit as follows.
  • Page 159 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. •...
  • Page 160 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
  • Page 161 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
  • Page 162 • When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal On → Off Stop (R.C. disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
  • Page 163  Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
  • Page 164: 11-2.Wall Mounted Type (Kgtb, 18-24Kmtb, Keta, And Keta-B)

    11-2. Wall mounted type (KGTB, 18-24KMTB, KETA, and KETA- External input and output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB Input External input External output Connector Input select signal Operation/Stop CN313/ Edge/Pulse Dry contact/...
  • Page 165 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 166 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  External input and output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 167 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
  • Page 168  Input signal type External input and output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and out- put PCB. The width of pulse must be longer than 200 msec.
  • Page 169 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Operation External input and 46-00...
  • Page 170 • When function setting is "Forced stop" mode – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Forced stop External input and 46-02 60-00 / 1 CN313 output PCB...
  • Page 171 • When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Operation External input and 46-03 60-00 / 1 CN313 Stop (R.C.
  • Page 172 • Forced thermostat off function Rotary SW on Function External input and External input Input signal Command setting / output PCB Thermostat 60-00 / 2 Off → On External input and output 60-09 / B CN313 Normal 60-10 / C On →...
  • Page 173  Control output function • Operation/Stop status Rotary SW on Function Output External input and External output Command setting / signal output PCB Off → On Operation External input and output 60-00 / 1 CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 174: 11-3.Wall Mounted Type (07-14Kmtb And Kmcc)

    11-3. Wall mounted type (07-14KMTB and KMCC) With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details.
  • Page 175 • Circuit diagram example • Contact capacity: DC 24 V or more, 10 Indoor unit mA or more. Communication kit Connected unit control PCB • *: Make the distance from the PCB to Example: Switch Connector the connected unit within 10 m. •...
  • Page 176 • Optional part Part name Model name Exterior External input wire External connect kit UTY-XWZXZ5 Communication kit UTY-TWBXF2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5). - 168 - 11-3.
  • Page 177 ¢ External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device.  Operation status output Air conditioner operation status signal can be output. •...
  • Page 178  Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 179: 11-4.Ceiling Type

    11-4. Ceiling type Rotary switch CN65 CN47 (Ext.in/out PCB) (Ext.out) Terminal (Ext.in) Fig. Indoor unit PCB Fig. External input and output PCB External Input connect kit External input External output Connector Input select signal (Optional parts) Operation/Stop — Terminal Dry contact Edge —...
  • Page 180  External input and output PCB The indoor unit Operation/Stop can be set by using the input terminal on the PCB.  Input select Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.) •...
  • Page 181 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 182 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
  • Page 183  Input signal type • Indoor unit Input signal type is only "Edge". Edge • External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
  • Page 184 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Pulse" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Input 1 Pulse Operation External input and...
  • Page 185 • When function setting is "Forced stop" mode – In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Forced stop Input of indoor unit Terminal On →...
  • Page 186 • When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal Stop (R.C.
  • Page 187  Forced thermostat off function Function Rotary SW of External External input Input signal Command setting / input and output PCB 60-00 / 2 Off → On Thermostat off 60-09 / B External input and output Input 1 60-10 / C Normal On →...
  • Page 188  Error status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Error 60-09 / B Output of indoor unit CN47 High → Low Normal Off → On Error 60-00 / 2 Output 1 On →...
  • Page 189  External heater output Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Heater on 60-11 / D Output of indoor unit CN47 High → Low Heater off 60-00 / 2 Off →...
  • Page 190: 11-5.Floor Type

    11-5. Floor type Indoor unit PCB CN 23 CN 21 CN 15 CN 14 P 190 External input External output Connector Input signal Operation/Stop CN14 Forced stop — Edge Forced thermostat off CN15 Operation status Indoor unit Error status CN20/CN21/ —...
  • Page 191 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m . •...
  • Page 192 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input Function Mode Indoor unit setting CN14 CN15...
  • Page 193 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 On → Off Stop 46-00 Input of indoor unit...
  • Page 194 • When function setting is "Operation/Stop"mode 2 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 Stop (R.C. On → Off disabled) 46-03 Input of indoor unit Off → On Operation 60-00 CN15...
  • Page 195  Control output function • Operation/Stop status Output Mode Function setting External output Command signal Low → High Operation 60-00 CN15 High → Low Stop Output of indoor unit Off → On Operation 60-00 CN20 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 196 • Indoor unit fan operation status Output Mode Function setting External output Command signal Low → High Fan run 60-10 CN15 High → Low Fan stop Output of indoor unit Off → On Fan run 60-00 CN22 On → Off Fan stop Output signal Condition...
  • Page 197 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 189 - 11-5.
  • Page 198 • Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 199: Group Connection

    12. Group connection NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 200 2. Set the R.C. address. (Function setting) • Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial setting of “00”.
  • Page 201: Remote Controller

    13. Remote controller 13-1. Wireless remote controller (AR-REW4E, AR-REM4E, and AR-REB1E) ¢ Overview • AR-REW4E Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button...
  • Page 202 To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current oper- ation. • AR-REM4E Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button...
  • Page 203 • AR-REB1E Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button CLOCK ADJUST button TIMER CANCEL button NOTE: Functions may differ by type of the indoor unit.
  • Page 204 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 205: 13-2.Wireless Remote Controller (Ar-Rew2E)

    13-2. Wireless remote controller (AR-REW2E) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 206 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 125 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 207: 13-3.Wireless Remote Controller (Ar-Rem7E)

    13-3. Wireless remote controller (AR-REM7E) ¢ Overview Signal transmitter MODE button FAN button 10 °C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 208 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 209: 13-4.Wireless Remote Controller (Uty-Lnty: Optional Part)

    13-4. Wireless remote controller (UTY-LNTY: Optional part) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button TIMER CANCEL button...
  • Page 210 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 211: 13-5.Ir Receiver Kit With Wireless Remote Controller (Uty-Lbtym: Optional Part)

    13-5. IR receiver kit with Wireless remote controller (UTY- LBTYM: Optional part) ¢ Overview Signal transmitter FAN button MODE button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button...
  • Page 212 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 213  IR receiver Unit: mm 13.6 57.4 13.6 11.5 18.5 Front view Side view Rear view Size (H × W × D) 145 × 90 × 30 Weight - 205 - 13-5. IR receiver kit with Wireless remote controller (UTY-LBTYM: Optional part) 13.
  • Page 214: 13-6.Wired Remote Controller (Uty-Rnnym: Optional Part)

    13-6. Wired remote controller (UTY-RNNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 215 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 216 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power  Wiring specifications Cable size Wire type Remarks Remote controller cable...
  • Page 217  When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 218: 13-7.Wired Remote Controller (Uty-Rlry: Optional Part)

    13-7. Wired remote controller (UTY-RLRY: Optional part) ¢ Overview a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Quiet...
  • Page 219 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 220 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: 9 × 4.5 Hole: 12.5 × 4.5 Hole: 6 × 4.5 Front view Side view Rear view Size (H × W × D) 120 ×...
  • Page 221: 13-8.Wired Remote Controller (Uty-Rvnym: Optional Part)

    13-8. Wired remote controller (UTY-RVNYM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 213 - 13-8.
  • Page 222 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 223 ¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight  Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 215 - 13-8.
  • Page 224 ¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
  • Page 225 3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
  • Page 226 4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
  • Page 227 5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. ¢...
  • Page 228  When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 229: 13-9.Wired Remote Controller (Uty-Rnryz*: Optional Part)

    13-9. Wired remote controller (UTY-RNRYZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. c LED lamp (operation indicator) d Touch panel display e Set temperature Operating temperature can be set. f Remote controller group name g Mode Operation mode can be set.
  • Page 230 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 231 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. [Unit : mm] 20.4 Model name UTY-RNRYZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) 120 × 120 × 20.4 Weight Input voltage DC 12...
  • Page 232: 13-10.Simple Remote Controller (Uty-Rsnym: Optional Part)

    13-10. Simple remote controller (UTY-RSNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 233 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 234 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
  • Page 235  When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 236: 13-11.Simple Remote Controller (Uty-Rsry And Uty-Rhry: Optional Parts)

    13-11. Simple remote controller (UTY-RSRY and UTY-RHRY: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
  • Page 237 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 238 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 30.0 30.0 Hole: 9 × 4.5 23.0 Hole: 6 × 4.5 Hole: 12.5 × 4.5 Front View Side View Rear View Size (H × W × D) 120 ×...
  • Page 239: Function Settings

    14. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 14-1. Compact cassette, Mini duct, Slim duct types indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
  • Page 240 ¢ DIP switch setting • SW100: Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. The slide switches are normally set to make the unit number 00. Remote Switch number controller...
  • Page 241: 14-2.Indoor Unit (Setting By Wireless Remote Controller)

    14-2. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 242 ¢ AR-REM4E (for Wall mounted type KGTB), AR-REW4E (for Wall mounted type KETA), AR-REW2E (for Wall mounted type KMTB), and AR-REM7E (for Floor type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller.
  • Page 243 To enter the function setting mode, while holding down the POWERFUL and TEMP. button, press the RESET button. POWERFUL TEMP. ( RESET Function setting mode display - 235 - 14-2. Indoor unit (setting by wireless remote controller) 14. Function settings...
  • Page 244 Select the function number by pressing the or the buttons. Each time the 10 °C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the POWERFUL button. (To return to the function number selection, press the POWERFUL button again.) Select the function number by pressing the or the...
  • Page 245 Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 2 short beeps NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 246  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 247  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
  • Page 248 ¢ AR-REB1E (for Wall mounted type KMCC)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details. 10°C HEAT button POWERFUL button Changes the displayed digits.
  • Page 249 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the POWERFUL button. (To return to the function number selection, press the POWERFUL button again.) Select the function number by pressing the or the...
  • Page 250 Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 2 short beeps NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 251  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 252  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 253 ¢ UTY-LNTY (for Compact cassette type) or AR-REJ1E (included in UTY-LBTYM for Duct type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
  • Page 254 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the ECONOMY button. (To return to the function number selection, press the ECONOMY button again.) Select the function number by pressing the or the...
  • Page 255 Press the button once to transmit the function setting information. 1 short beep will be emit- ted from the indoor unit or the IR receiver when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 1 short beep NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 256  Setting up each indoor unit Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from 1. to 2. and 8. need to be performed.  Resetting the power after setting up all indoor units Important: •...
  • Page 257  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 258: 14-3.Indoor Unit (Setting By Wired Remote Controller)

    14-3. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 259 ¢ UTY-RNNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 260 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 261 ¢ UTY-RLRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 262 Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good...
  • Page 263 ¢ UTY-RVNYM  Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
  • Page 264 Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
  • Page 265 When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
  • Page 266 ¢ UTY-RNRYZ*  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 267 “Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
  • Page 268 Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
  • Page 269: 14-4.Indoor Unit (Setting By Simple Remote Controller)

    14-4. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 270 ¢ UTY-RSNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 271 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 272  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 273 ¢ UTY-RSRY/UTY-RHRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 274 Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
  • Page 275 Setting results are displayed after data transmission. Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se- lection screen.
  • Page 276: 14-5.Function Details

    14-5. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Medium Wall mounted Function...
  • Page 277 1) Remote controller address setting (for Wall-mounted type only) NOTES: • Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. • This setting is configurable only by wireless remote controller, but not configurable by Polar 3- wired remote controller.
  • Page 278 3) Ceiling height (for Compact cassette type and Ceiling type only) Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 3. "Dimensions"...
  • Page 279 6) Static pressure (for Mini duct type and Slim duct type) Select the appropriate static pressure according to the installation conditions. For mini duct type: Function number Setting value Setting description Factory setting 0 Pa 10 Pa 20 Pa 30 Pa 40 Pa 50 Pa Standard...
  • Page 280 8) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 281 9) Room temperature control for wired remote controller sensor (for other than Floor type) Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 282 12) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 13) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 283 16) Switching functions for external output terminal (For other than KM and KE models in Wall-mounted type) Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦...
  • Page 284: 14-6.Wired Remote Controller (Uty-Rnnym)

    14-6. Wired remote controller (UTY-RNNYM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 285  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 286: 14-7.Wired Remote Controller (Uty-Rvnym)

    14-7. Wired remote controller (UTY-RVNYM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 287: 14-8.Wired Remote Controller (Uty-Rlry)

    14-8. Wired remote controller (UTY-RLRY) DIP switch Memory backup setting ¢ Switch location Front case (back side) Set the DIP switch to ON ¢ Dip switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 288: 14-10.Simple Remote Controller (Uty-Rsnym)

    14-10. Simple remote controller (UTY-RSNYM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 289: Accessories

    15. Accessories 15-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose insulation Operating manual Hose band (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Template (Carton top) (small) M10 nut A...
  • Page 290: 15-2.Mini Duct Type

    15-2. Mini duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, and ARXG14KSLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose Operating manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation...
  • Page 291 ¢ Model: ARXG18KSLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose Operating manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small) Insulation...
  • Page 292: 15-3.Slim Duct Type

    15-3. Slim duct type ¢ Models: ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (Large) Installation manual Cable tie (Small) Installation template Drain hose Washer Hose band Coupler heat insulation Drain hose insulation B (Large) Coupler heat insulation...
  • Page 293: 15-4.Medium Static Pressure Duct Type

    15-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (medium) Operating manual Cable tie (small) (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Hanger (small) M10 nut A...
  • Page 294: 15-5.Wall Mounted Type

    15-5. Wall mounted type ¢ Models: ASYG07-14KGTB, ASYG07-14KMTB, and ASYG07-14KMCC Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder...
  • Page 295 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Tapping screw (large) Installation manual Tapping screw (small) Remote controller Battery Remote controller Filter holder holder Cloth tape Air cleaning filters Wall hook bracket - 287 - 15-5.
  • Page 296 ¢ Models: ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG14KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, and ASYG14KETA-B Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters...
  • Page 297: 15-6.Ceiling Type

    15-6. Ceiling type ¢ Models: ABYG18KRTA and ABYG22KRTA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Insulation Operating manual Drain hose (CD-ROM) Installation manual Hose band Template Cable tie (large) M10 nut A Cable tie (small) (with flange) M10 nut B Remote controller cable (with spring lock...
  • Page 298: 15-7.Floor Type

    15-7. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual (CD- Operating manual ROM) Installation manual Cloth tape Wall hook bracket Tapping screws (large) Remote controller Tapping screws (small) Battery Air cleaning filters Remote controller holder - 290 -...
  • Page 299: Optional Parts

    16. Optional parts 16-1. Controllers ¢ Lineup Type Wireless remote controller Indoor unit type UTY- REM4E REM7E REB1E REW2E REW4E LNTY Compact cassette — — — — — ◌ Mini duct — — — — — — Slim duct — —...
  • Page 300 Type IR receiver kit with Wireless remote Simple remote controller Indoor unit type controller UTY- UTY-LBTYH UTY-RSNYM UTY-RSRY UTY-RHRY LBTYM Compact cassette — — ◌ ◌ ◌ Mini duct ◌ — ◌ ◌ ◌ Slim duct ◌ — ◌ ◌ ◌...
  • Page 301 ¢ Parts Wireless remote controller AR-REW4E AR-REM4E AR-REB1E UTY-LNTY Wireless remote controller AR-REW2E AR-REM7E Wired remote controller UTY-RNNYM UTY-RVNYM UTY-RLRY UTY-RNRYZ* IR receiver kit with Wireless remote controller Simple remote controller UTY-LBTYM UTY-LBTYH UTY-RSNYM UTY-RSRY UTY-RHRY - 293 - 16-1. Controllers 16.
  • Page 302: 16-2.Cassette Grille

    16-2. Cassette grille ¢ Lineup Indoor unit type Model Compact cassette UTG-UFYF-W ¢ Part Cassette grille UTG-UFYF-W - 294 - 16-2. Cassette grille 16. Optional parts...
  • Page 303: 16-3.Others

    16-3. Others ¢ Lineup Type Insulation Air outlet Half kit for Fresh air External input and shutter concealed Indoor unit type high intake kit output PCB plate humidity UTR- UTZ- UTY- UTZ-VXAA UTR-STA UTY-XCSX YDZB KXGC XCSXZ2 Compact cassette ◌ ◌...
  • Page 304 Type MODBUS Remote Indoor unit type Network converter converter converter sensor unit UTY-VKSX UTY-VTGX UTY-VTGXV UTY-VMSX UTY-XSZX Compact cassette ◌ ◌ ◌ ◌ — Mini duct ◌ ◌ ◌ ◌ ◌ Slim duct ◌ ◌ ◌ ◌ ◌ Medium static pressure duct ◌...
  • Page 305 NOTE: Combined use of MODBUS converter, KNX converter, and Wireless LAN adapter is not al- lowed. ¢ Parts Air outlet shutter plate Insulation kit for high humidity Model: UTR-YDZB Model: UTZ-KXGC Insulation Fresh air intake kit External connect kit Model: UTZ-VXAA Model: UTY-XWZXZG External connect kit External connect kit...
  • Page 306 Remote sensor unit Auto louver grille kit Model: UTY-XSZX Models: UTD-GXTA-W Wireless LAN adapter Wireless LAN adapter Models: UTY-TFSXZ1 Models: UTY-TFSXW1 Wireless LAN adapter Half concealed kit Models: UTY-TFSXF2 Models: UTR-STA Square flange Round flange Models: UTD-SF045T Models: UTD-RF204 Long-life filter Drain pump unit Models: UTD-LF25NA Models: UTZ-PX1NBA...
  • Page 307: Indoor Unit Installation Precautions

    17. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 308 Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 30 °C RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
  • Page 309 Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 30 °C Figure 17-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
  • Page 310 - 302 - 17-2. Points to remember when installing 17. Indoor unit installation precautions...
  • Page 311: Part 2. Outdoor Unit (4 Units Type)

    Part 2. OUTDOOR UNIT (4 UNITS TYPE) MULTI-SPLIT TYPE: AOYG30KBTA4...
  • Page 312: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG30KBTA4 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ASYG07KMCC ×4 Rated Btu/h 27,300 Cooling 2.4—10.1 Min.—Max. Btu/h 8,200—34,500 Capacity Rated Btu/h 32,800 Heating 3.0—11.2 Min.—Max.
  • Page 313 Specifications for ErP Lot10 Model name AOYG30KBTA4 Cooling Energy efficiency class Heating (Average) Cooling 8.0 (35 °C) Pdesign Heating (Average) 6.5 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 1,978 Cooling Sound power level HIGH dB (A) Heating...
  • Page 314: Dimensions

    2. Dimensions 2-1. Model: AOYG30KBTA4 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 306 - 2-1. Model: AOYG30KBTA4 2. Dimensions...
  • Page 315: Installation Space

    3. Installation space 3-1. Model: AOYG30KBTA4 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 316  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 317  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 318: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOYG30KBTA4 Pressure switch CONDENSER - 310 - 4-1. Model: AOYG30KBTA4 4. Refrigerant circuit...
  • Page 319: Wiring Diagram

    5. Wiring diagram 5-1. Model: AOYG30KBTA4 - 311 - 5-1. Model: AOYG30KBTA4 5. Wiring diagram...
  • Page 320: Capacity Table

    6. Capacity table 6-1. Combinations ¢ Model: AOYG30KBTA4  Cooling Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max.
  • Page 321 Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.47 1.47 2.53 2.53 8.00 10.1...
  • Page 322  Heating Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class —...
  • Page 323 Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class 1.40 1.80 2.80 3.60 9.60...
  • Page 324: Cooling Capacity

    6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG30KBTA4 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 325 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.94 1.97 1.99 10.1 2.01 10.8 2.03...
  • Page 326 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.94 1.97 1.99 10.1 2.01 10.8 2.03...
  • Page 327 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.71 1.74 1.76 1.78 1.80 10.2 1.81...
  • Page 328  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 329 Model: AUXG18KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.88 5.37 3.28 5.66 3.78 6.06 4.24 6.48 4.64 6.68 5.32 -5.0 4.75...
  • Page 330  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 331 Model: ARXG18KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68 5.47 -5.0 4.75...
  • Page 332  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 333 • Values mentioned in the table are based on the following conditions: – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)  Medium static pressure duct type Model: ARXG22KMLB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0...
  • Page 334  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78...
  • Page 335 Model: ASYG18KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 3.21 5.37 3.65 5.66 4.21 6.06 4.73 6.48 5.17 6.68 5.92 -5.0 4.75...
  • Page 336 Model: ASYG07KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 337 Model: ASYG07KMCC Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 338 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 339  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68...
  • Page 340  Floor type Model: AGYG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 341: Heating Capacity

    6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG30KBTA4 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96...
  • Page 342 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96 3.02 3.08 3.14 3.20 -10.0 -11.0 3.24 3.31 3.38 3.45 3.51 -5.0 -7.0 3.13 3.20 3.26 3.33 3.39 -2.0...
  • Page 343 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96 3.02 3.08 3.14 3.20 -10.0 -11.0 3.24 3.31 3.38 3.45 3.51 -5.0 -7.0 3.13 3.20 3.26 3.33 3.39 -2.0...
  • Page 344 NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
  • Page 345  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 346 Model: AUXG22KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.66 4.55 4.44 4.33 4.22 -10.0 -11.0 5.80 5.67 5.53 5.39 5.25 -5.0 -7.0 6.91 6.74 6.58 6.41 6.25 -2.0 8.12 7.93 7.73 7.54 7.35 8.93 8.71...
  • Page 347  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 348 Model: ARXG18KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 349  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 350 • TC: Total Capacity (kW) • Values mentioned in the table are based on the following conditions: – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)  Medium static pressure duct type Model: ARXG22KMLB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0...
  • Page 351  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 352 Model: ASYG18KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 353 Model: ASYG07KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 354 Model: ASYG07KMCC Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 355 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94...
  • Page 356  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96...
  • Page 357  Floor type Model: AGYG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.97 1.93 1.88 1.83 1.79 -10.0 -11.0 2.46 2.40 2.34 2.28 2.22 -5.0 -7.0 2.92 2.86 2.79 2.72 2.65 -2.0 3.44 3.36 3.28 3.19...
  • Page 358: Capacity Compensation Rate For Pipe Length And Height Difference

    7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOYG30KBTA4 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 359 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.956 0.942 0.928 — — 0.977 0.963 0.950 0.936 Indoor unit is higher than outdoor unit *1 — 0.992 0.985 0.971 0.957 0.943 1.003 0.996 0.989 0.975 0.961 0.947 1.007 1.000 0.993...
  • Page 360 ¢ Indoor unit: 14,000 Btu/h Pipe length Cooling — — — 0.955 0.937 0.922 — — 0.974 0.962 0.945 0.930 Indoor unit is higher than outdoor unit *1 — 0.992 0.982 0.970 0.952 0.937 0.999 0.996 0.986 0.974 0.956 0.941 1.005 1.000 0.990...
  • Page 361 ¢ Indoor unit: 22,000 Btu/h Pipe length Cooling — — — 0.978 0.969 0.953 — — 0.986 0.986 0.977 0.961 Indoor unit is higher than outdoor unit *1 — 0.992 0.994 0.994 0.984 0.968 0.993 0.996 0.998 0.998 0.988 0.972 0.997 1.000 1.002...
  • Page 362: Additional Charge Calculation

    8. Additional charge calculation 8-1. Model: AOYG30KBTA4 Refrigerant type Refrigerant amount 2,200 Refrigerant charge Total pipe length 40 or less 70 (Max.) 20 g/m Additional charge amount - 354 - 8-1. Model: AOYG30KBTA4 8. Additional charge calculation...
  • Page 363: Airflow

    9. Airflow 9-1. Model: AOYG30KBTA4  Cooling 2,400 1,413  Heating 2,950 1,736 - 355 - 9-1. Model: AOYG30KBTA4 9. Airflow...
  • Page 364: Operation Noise (Sound Pressure)

    10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOYG30KBTA4  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 365: Electrical Characteristics

    11. Electrical characteristics Model name AOYG30KBTA4 Voltage 230 ~ Power supply Frequency 18.5 Maximum operating current * Starting current Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 366: Safety Devices

    12. Safety devices Model Type of Protection form protection AOYG30KBTA4 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
  • Page 367: Function Settings

    13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 368 ¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
  • Page 369 ¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 370: 13-2.Outdoor Unit Low Noise Operation Function (Option)

    13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
  • Page 371: Check And Test

    14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 372 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
  • Page 373 After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 374 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
  • Page 375 c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
  • Page 376 ¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
  • Page 377: 14-2.Test Run

    14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 378: 14-3.Error Code

    Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
  • Page 379 ¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
  • Page 380 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
  • Page 381: 14-4.Pump Down

    14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant piping. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
  • Page 382 7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
  • Page 383: Accessories

    15. Accessories 15-1. Model: AOYG30KBTA4 Part name Exterior Q’ty Part name Exterior Q’ty Adapter K: mm (in) Installation manual 12.70 (1/2) to 9.52 (3/8) Drain pipe - 375 - 15-1. Model: AOYG30KBTA4 15. Accessories...
  • Page 384: Outdoor Unit Installation Precautions

    16. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 16-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 385: Part 3. Outdoor Unit (5 Units Type)

    Part 3. OUTDOOR UNIT (5 UNITS TYPE) MULTI-SPLIT TYPE: AOYG36KBTA5...
  • Page 386: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG36KBTA5 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ASYG07KMCC ×5 Rated Btu/h 32,400 Cooling 3.0—11.0 Min.—Max. Btu/h 10,200—37,500 Capacity 10.6 Rated Btu/h 36,200 Heating 3.5—12.0...
  • Page 387 Specifications for ErP Lot10 Model name AOYG36KBTA5 Cooling Energy efficiency class Heating (Average) Cooling 9.5 (35 °C) Pdesign Heating (Average) 7.0 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 2,130 Cooling Sound power level HIGH dB (A) Heating...
  • Page 388: Dimensions

    2. Dimensions 2-1. Model: AOYG36KBTA5 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 380 - 2-1. Model: AOYG36KBTA5 2. Dimensions...
  • Page 389: Installation Space

    3. Installation space 3-1. Model: AOYG36KBTA5 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 390  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 391  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 392: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOYG36KBTA5 Pressure switch CONDENSER - 384 - 4-1. Model: AOYG36KBTA5 4. Refrigerant circuit...
  • Page 393: Wiring Diagram

    5. Wiring diagram 5-1. Model: AOYG36KBTA5 - 385 - 5-1. Model: AOYG36KBTA5 5. Wiring diagram...
  • Page 394: Capacity Table

    6. Capacity table 6-1. Combinations ¢ Model: AOYG36KBTA5  Cooling Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max.
  • Page 395 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 1.90 1.90 1.90 3.80 —...
  • Page 396 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.33 1.33 1.71 1.71 3.42 9.50...
  • Page 397  Heating Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — —...
  • Page 398 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — 1.55 1.55 2.64 4.86 —...
  • Page 399 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class 1.50 1.95 1.95 2.60 2.60 10.60...
  • Page 400: Cooling Capacity

    6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG36KBTA5 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 401 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.31 2.36 10.3 2.37 11.0 2.40 11.8...
  • Page 402 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.31 2.36 10.3 2.37 11.0 2.40 11.8...
  • Page 403 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.31 2.36 10.3 2.37 11.0 2.40 11.8...
  • Page 404  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 405 Model: AUXG18KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 2.94 5.48 3.35 5.78 3.86 6.19 4.33 6.62 4.74 6.82 5.43 -5.0 4.85...
  • Page 406  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 407 Model: ARXG18KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.02 5.48 3.45 5.78 3.97 6.19 4.46 6.62 4.87 6.82 5.58 -5.0 4.85...
  • Page 408  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 409 • Values mentioned in the table are based on the following conditions: – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)  Medium static pressure duct type Model: ARXG22KMLB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0...
  • Page 410  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78...
  • Page 411 Model: ASYG18KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.27 5.48 3.73 5.78 4.30 6.19 4.83 6.62 5.28 6.82 6.05 -5.0 4.85...
  • Page 412 Model: ASYG07KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 413 Model: ASYG07KMCC Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 414 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 415  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.02 5.48 3.45 5.78 3.97 6.19 4.46 6.62 4.87 6.82...
  • Page 416  Floor type Model: AGYG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 417: Heating Capacity

    6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG36KBTA5 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88...
  • Page 418 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88 2.94 3.00 3.06 3.12 -10.0 -11.0 3.25 3.32 3.39 3.46 3.53 -5.0 -7.0 2.93 2.99 3.05 3.11 3.17 -2.0...
  • Page 419 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88 2.94 3.00 3.06 3.12 -10.0 -11.0 3.25 3.32 3.39 3.46 3.53 -5.0 -7.0 2.93 2.99 3.05 3.11 3.17 -2.0...
  • Page 420 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.50 2.56 2.61 2.66 2.71 -10.0 -11.0 2.83 2.89 2.95 3.01 3.07 -5.0 -7.0 2.55 2.60 2.65 2.71 2.76 -2.0...
  • Page 421  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 422 Model: AUXG22KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 5.55 5.41 5.28 5.15 5.02 -10.0 -11.0 6.44 6.29 6.13 5.98 5.83 -5.0 -7.0 6.80 6.64 6.48 6.31 6.15 -2.0 7.78 7.60 7.41 7.23 7.04 8.95 8.73...
  • Page 423  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 424 Model: ARXG18KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 425  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 426 • TC: Total Capacity (kW) • Values mentioned in the table are based on the following conditions: – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)  Medium static pressure duct type Model: ARXG22KMLB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0...
  • Page 427  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 428 Model: ASYG18KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 429 Model: ASYG07KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 430 Model: ASYG07KMCC Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 431 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94...
  • Page 432  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73...
  • Page 433  Floor type Model: AGYG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.34 2.29 2.23 2.18 2.12 -10.0 -11.0 2.72 2.66 2.59 2.53 2.46 -5.0 -7.0 2.87 2.80 2.74 2.67 2.60 -2.0 3.29 3.21 3.13 3.05...
  • Page 434: Capacity Compensation Rate For Pipe Length And Height Difference

    7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOYG36KBTA5 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 435 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.956 0.942 0.928 — — 0.977 0.963 0.950 0.936 Indoor unit is higher than outdoor unit *1 — 0.992 0.985 0.971 0.957 0.943 0.996 0.996 0.989 0.975 0.961 0.947 1.000 1.000 0.993...
  • Page 436 ¢ Indoor unit: 14,000 Btu/h Pipe length Cooling — — — 0.955 0.937 0.922 — — 0.974 0.962 0.945 0.930 Indoor unit is higher than outdoor unit *1 — 0.992 0.982 0.970 0.952 0.937 0.996 0.996 0.986 0.974 0.956 0.941 1.000 1.000 0.990...
  • Page 437 ¢ Indoor unit: 22,000 Btu/h Pipe length Cooling — — — 0.978 0.969 0.953 — — 0.986 0.986 0.977 0.961 Indoor unit is higher than outdoor unit *1 — 0.992 0.994 0.994 0.984 0.968 0.996 0.996 0.998 0.998 0.988 0.972 1.000 1.000 1.002...
  • Page 438: Additional Charge Calculation

    8. Additional charge calculation 8-1. Model: AOYG36KBTA5 Refrigerant type Refrigerant amount 2,500 Refrigerant charge Total pipe length 40 or less 75 (Max.) 20 g/m Additional charge amount - 430 - 8-1. Model: AOYG36KBTA5 8. Additional charge calculation...
  • Page 439: Airflow

    9. Airflow 9-1. Model: AOYG36KBTA5  Cooling 2,450 1,501  Heating 2,900 1,766 - 431 - 9-1. Model: AOYG36KBTA5 9. Airflow...
  • Page 440: Operation Noise (Sound Pressure)

    10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOYG36KBTA5  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 441: Electrical Characteristics

    11. Electrical characteristics Model name AOYG36KBTA5 Voltage 230 ~ Power supply Frequency 20.0 Maximum operating current * Starting current 11.1 Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 442: Safety Devices

    12. Safety devices Model Type of Protection form protection AOYG36KBTA5 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
  • Page 443: Function Settings

    13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 444 ¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
  • Page 445 ¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 446: 13-2.Outdoor Unit Low Noise Operation Function (Option)

    13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
  • Page 447: Check And Test

    14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 448 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
  • Page 449 After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 450 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
  • Page 451 c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
  • Page 452 ¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
  • Page 453: 14-2.Test Run

    14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 454: 14-3.Error Code

    Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
  • Page 455 ¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
  • Page 456 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
  • Page 457: 14-4.Pump Down

    14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant piping. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
  • Page 458 7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
  • Page 459: Accessories

    15. Accessories 15-1. Model: AOYG36KBTA5 Part name Exterior Q’ty Part name Exterior Q’ty Adapter K: mm (in) Installation manual 12.70 (1/2) to 9.52 (3/8) Adapter H: mm (in) Drain pipe 9.52 (3/8) to 12.70 (1/2) Cable tie (small) - 451 - 15-1.
  • Page 460: Optional Parts

    16. Optional parts Exterior Part name Model name Summary Set temperatures on timers to best meet individuals’ needs. Includes a large backlit LCD and 4-way navigation pad. Remote controller cable: 0.33 mm² (22AWG) NOTES: • The remote controller cable supplied with this controller is for indoor use.
  • Page 461: Outdoor Unit Installation Precautions

    17. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.