6-2. Outdoor unit
Connector
P580
Low noise mode
PA580
P590
PA590
¢ External input
With using external input function, on/off status of "Low noise mode" and "Peak cut mode" can be
specified by the external signal.
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in nor-
mal operating condition:
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE: Product performance may drop depending on some conditions such as the outdoor temper-
ature.
• Circuit diagram example
Outdoor unit
control PCB
Connector
1
2
1
2
Input signal
Low noise mode
• Optional part
Part name
External connect kit
6-2. Outdoor unit
Input
Peak cut mode
—
—
Connected unit
(Locally purchased)
Example: Switch
10m*
Signal
On
Off
On
Off
Model name
UTY-XWZXZ3
Output
—
—
Error status
Compressor status
• Contact capacity: DC 24 V or more, 10 mA or
more.
• *: Make the distance from the PCB to the con-
nected unit within 10 m.
• Construct a circuit as shown in this figure with
using optional parts mentioned below.
• Input signal: On in "Low noise mode"
• Input signal: Off in normal operation
• To set the level of "Low noise mode", refer to
"Low noise mode"
- 135 -
Remarks
See external input/output settings
for details.
on page 159.
Exterior
External input wire
6. External input and output