Retry Function (Pr. 65, Pr. 67 To Pr. 69) - Mitsubishi FR-E540-0.4K-EC Instruction Manual

Transistorized inverter
Table of Contents

Advertisement

<Setting2>
! Set the parameters when it is desired to improve the performance in the shortest
acceleration/deceleration mode.
(1) Pr. 61 "reference I for intelligent mode"
Setting
9999 (factory setting)
0 to 500A
(2) Pr. 62 "ref. I for intelligent mode accel"
The reference current setting can be changed.
Setting
9999 (factory setting)
0 to 200%
(3) Pr. 63 "ref. I for intelligent mode decel"
The reference current setting can be changed.
Setting
9999 (factory setting)
0 to 200%
Note: Pr. 61 to Pr. 63 are only valid when any of "1, 2, 11, 12" are selected for
Pr. 60.
" " Retry function (Pr. 65, Pr. 67, Pr. 68, Pr. 69)

4.2.25 Retry function (Pr. 65, Pr. 67 to Pr. 69)

Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When any protective function (major fault) is activated and the inverter stops its output,
the inverter itself resets automatically and performs retries. You can select whether
retry is made or not, alarms reset for retry, number of retries made, and waiting time.
Parameter
Factory
Number
Setting
65
67
68
69
Referenced from rated inverter current
Referenced from setting (rated motor current)
150% (180%) is the limit value.
The setting of 0 to 200% is the limit value.
150% (180%) is the limit value.
The setting of 0 to 200% is the limit value.
Setting Range
0
0 to 3
0
0 to 10, 101 to 110
1 s
0.1 to 360 s
0
0
Reference Current
Reference Current
Reference Current
96
PARAMETERS

Advertisement

Table of Contents
loading

Table of Contents