 Outline of instructions
• Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth.
Connect the equipment to the earth (ground) securely.
• Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
• Use the cable sizes on
page 44
• Surrounding air temperature: 40°C maximum
If conditions are different from the above, select appropriate wire according to EN 60204-1 or IEC 60364-5-52.
• Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening the
screw, be careful not to damage the threads.
• For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on
• A large leakage current flows into the protective earth (ground) conductor. The amount of current leakage from the FR-
CC2 and FR-A872 measures 20 mA at maximum (in AC/DC current measuring range specified in IEC 60990). Do not use
earth (ground) wires smaller than those specified in national and local safety regulations regarding leakage currents.
• Use the molded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
• DC current may flow from the inverter to a protective earth (ground) conductor. When using a residual current device (RCD)
or residual current monitor (RCM), connect a type B RCD or RCM to the power supply side.
• Use the inverter under the conditions of overvoltage category II (regardless of the earth (ground) condition of the power
supply), or overvoltage category III (inverters must be used with the earth-neutral system power supply) specified in IEC
60664.
To use the inverter under the conditions of pollution degree 2, install it in the enclosure of IP2X or higher.
To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• On the input and output of the inverter and the converter unit, use cables of the size and type set forth in EN 60204-1 or
IEC 60364-5-52.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30 VDC, 0.3 A. (Relay
output has basic isolation from the internal circuit of the inverter and the converter unit.)
• Control circuit terminals on
• Environment (For the details, refer to
Surrounding air temperature
-10°C to +40°C
Humidity
95% RH or less
Maximum altitude
4000 m
*1
For installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
 Branch circuit protection
To protect the internal circuit of the inverter or the converter unit against a short circuit, refer to the following table and
provide appropriate fuses on the input side.
Converter model
Fuse model
FR-CC2-N450K-P
170M6xx5
FR-CC2-N500K-P
170M6xx5
FR-CC2-N560K-P
170M6xx6
*1
"xx" in a model name is "41, 46, 51, or 56".
 Short circuit ratings
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 690 V maximum.
under the following conditions.
page 32
are safely isolated from the main circuit.
page
26.)
During operation
*1
*1
Manufacturer
Bussmann
Bussmann
Bussmann
Fuse
R/L1
S/L2
T/L3
Fuse connection diagram
In storage
-20°C to +65°C
95% RH or less
4000 m
Fuse rating (A)
700 V, 1100 A
700 V, 1100 A
700 V, 1250 A
Fuse
R/L1
S/L2
T/L3
7.1 Instructions for compliance with the EU Directives
page
44.
During transportation
-20°C to +65°C
95% RH or less
10000 m
125
7. APPENDIX
1
2
3
4
5
6
7
8
9
10