Mitsubishi Electric FR-A872-P Instruction Manual page 120

Table of Contents

Advertisement

Pulse train
output (FM type
inverter)
For indication
Current output
on external
(CA type
meters
inverter)
Voltage output
Status
monitoring
Operation
panel (FR-
DU08)
Fault record
Fault
Protective function
Alarm,
Warning, Error
message
*6
Noise
Surrounding air temperature
Surrounding air humidity
*3
Storage temperature
Ambience
Altitude/vibration
*1
Available when a Vector control compatible option is installed.
*2
In the initial setting, the starting torque is limited to 150% by the torque limit level.
*3
Applicable to conditions for a short time, for example, in transit.
*4
For installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
*5
Not activated in the inverter in the initial state.
*6
Values measured 1 m in front of the inverter and 1.6 m from the floor.
Max. 2.4 kHz via one terminal (for the indication of inverter output frequency).
The item for monitoring can be changed using Pr.54 FM/CA terminal function selection.
Max. 20 mADC via one terminal (for the indication of inverter output frequency).
The item for monitoring can be changed using Pr.54 FM/CA terminal function selection.
Max. 10 VDC via one terminal (for the indication of inverter output frequency).
The item for monitoring can be changed using Pr.158 AM terminal function selection.
Output frequency, output current, output voltage, and frequency setting value are monitored.
The item for monitoring can be changed using Pr.52 Operation panel main monitor selection.
When a protective function is activated, a fault indication is displayed and the output voltage, output
current, output frequency, cumulative energization time, date (year, month, day) and time at the
occurrence of the fault are stored. Each fault is recorded and the last 8 records can be displayed.
Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during
deceleration or stop, Overcurrent trip, Regenerative overvoltage trip during acceleration,
Regenerative overvoltage trip during constant speed, Regenerative overvoltage trip during
deceleration or stop, Overvoltage trip, Inverter overload trip (electronic thermal relay function), Motor
overload trip (electronic thermal relay function), Heat sink overheat, Undervoltage, Stall prevention
stop, Output side earth (ground) fault overcurrent, Output phase loss, External thermal relay
*5
operation
, PTC thermistor operation
slave 1 fault, Parallel operation slave 2 fault, Parameter storage device fault (control circuit board),
Parameter storage device fault (main circuit board), PU disconnection, CPU fault, Operation panel
power supply short circuit/RS-485 terminals power supply short circuit, 24 VDC power fault, Abnormal
output current detection, Communication fault, Analog input fault, USB communication fault, Safety
circuit fault, Overspeed occurrence
*1*5
Excessive position fault
, Brake sequence fault
*5
fault
, Opposite rotation deceleration fault
Fan alarm, Stall prevention (overcurrent), Stall prevention (overvoltage), Electronic thermal relay
function pre-alarm, PU stop, Speed limit indication
fault, Parameter copy, Safety stop, Maintenance signal output
*5
setting error
, Home position return uncompleted
Parameter write error, Copy operation error, 24 V external power supply operation
74 dB (single-unit operation)
-10°C to +40°C (non-freezing)
95% RH or less (non-condensing) (With circuit board coating (conforming to IEC 60721-3-3 3C2/3S2)
-20°C to +65°C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
*4
Maximum 4000 m
. Frequency range 10 to 57 Hz: maximum amplitude 0.075 mm. Frequency range
57 to 150 Hz: maximum acceleration speed 1G.
*5
, Option fault, Communication option fault, Parallel operation
*5
, Speed deviation excess detection
*5
, 4 mA input fault
*5
, Internal circuit fault
*5
, Continuous operation during communication
*5
, USB host error, Home position return
*5
, Operation panel lock
*1*5
*1*5
, Signal loss detection
,
*5
*5
, Pre-charge fault
, PID signal
*5
*5
, Password locked
,
6. SPECIFICATIONS
6.2 Common specifications
1
2
3
4
5
6
7
8
9
10
119