Certification
6.2 EMC and environmental type tests
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
IEC 60255-27
a
Siemens-specified severity levels
72
Test
Damped oscillating
magnetic field
Voltage dips
and interrupts
Mains frequency
voltage
Ripple on DC
power supply
Damped
oscillatory wave
Voltage dips
and interrupts
Dielectric strength
HV impulse
Description
Enclosure ports
AC power ports
Signal ports
DC power ports
AC power ports
DC power ports
Signal ports
DC power ports
AC power ports
DC power ports
Signal ports
DC power ports
AC power ports
Signal ports
DC power ports
AC power ports
PoE power ports
Test levels
Severity levels
1000 A/m for 1 s
100 A/m for
1 s (100 kHz
and 1 MHz)
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
30 V for 60 s
300 V for 1 s
30 V for 60 s
300 V for 1 s
30 V for 60 s
300 V for 1 s
15%
2.5 kV
common mode
2.5 kV
common mode
1.0 kV
differential mode
2.5 kV
common mode
1.0 kV
differential mode
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (fail-safe
relay output)
2.9 kVdc
2 kV
5 kV (fail-safe
relay output)
5 kV
5 kV
1 kV
RUGGEDCOM RST2428P
Equipment Manual, 10/2023, C79000-G8976-1528-01