Screen
o
SUPPLY SEN
180
F
o
RETURN SEN
150
F
Press v once.
o
CH SET
180
F
o
SUPPLY SEN
122
F
Press v once.
CH DEMAND
OFF
BOILER
Press v once.
0-10 SIGNL ON
*
Press v once.
o
CAS SET
190
F
o
SYSTEM
112
F
Press v once.
o
DHW SET
119
F
o
DHW
117
F
Press v once.
o
OUTDOOR
11
F
o
FLUE
95
F
Press v once.
whl-428-r1 Rev. 001 Rel. 012 Date 7.21.20
Description
This is the first screen that appears
after pressing >, and shows the
actual
temperatures
measured
by the supply and return sensors.
NOTE: If the boiler is configured to
use a 0 – 10 volt input, the return
sensor is disabled and the second
line of the display will be blank.
The screen displays the current
central heating temperature set
point on the top line. NOTE: This
temperature set point may vary
from what was set in the boiler
settings if an outdoor sensor is used.
The actual temperature measured
by the supply sensor is displayed on
the bottom line.
This screen displays the central heat
demand set for the cascade system.
Shows if 0-10 volt is enabled.
This screen appears only when
the boiler is set as a Master Boiler.
This screen displays the cascade set
o
point (maximum 190
F) on the top
line. The system sensor reading is
on the second line. The control will
cascade the boilers up to this set
point depending on demand.
Displays
the
current
temperature set point on the
top line. The actual temperature
measured by the tank or return
sensor (Westinghouse 7250P-325)
is displayed on the bottom line. If
a mechanical aquastat is used in
place of the recommended sensor,
the second line will display 'OFF'
in place of the temperature if the
aquastat measures close to its set
temperature, or 'ON' if the aquastat
temperature is too low.
The current outdoor temperature
is displayed on the top line. If there
is no outdoor sensor connected
to the boiler, this line will display
"OFF" in place of the temperature.
If the outdoor sensor is shorted,
this line will display "ON" in place
of the temperature. The second
line displays the current boiler flue
temperature.
FLAME
FAN SPEED
3497 RPM
Press v once.
0-10 V
*
Press v once.
BUS COMM
NO CONN
Press v once.
POWER ON
CH ON
Press v once.
DHW ON
GOOD IGNIT
tank
Press v once.
SYS CH ON
SYS DHW ON
Table 22 - Boiler Control Status Menu Screens
The next ten screens display the last ten boiler lockout faults. Press v
to scroll through the faults from most recent to oldest.
Screen
FAULT HISTORY
07/27/2009
5:19A
Press v once.
FAULT HISTORY
08/28/2009
Fr 5:19A
Press v once.
This screen displays boiler flame
0.0uA
current on the top line. The second
line displays boiler fan speed.
The top line displays the voltage
on the optional input. This voltage
0.0V
is only relevant if an external 0-10
volt signal is being used to control
the boiler.
This display shows the status of
the communication bus between
multiple boilers. If in a single
boiler configuration, the display
will show 'NO CONN' . In a multiple
boiler configuration, if this is the
Master Boiler and other boilers are
connected to the communication
bus and powered, this screen will
show the address of each boiler
connected to the bus.
The top line indicates the amount
of hours the boiler has been
0H
powered over its life. The second
0H
line indicates how many hours the
burner has been on for central heat
demand over its life.
The top line indicates the hours the
burner has been on for hot water
0H
demand over the boiler's life. The
1X
second line indicates how many
times the burner has successfully
ignited over the boiler's life.
This screen displays how many
0H
hours the boiler has run to meet
0H
central heat and DHW demand.
Description
This screen displays the most recent
boiler control lockout fault. The
1
top line will alternate between the
Mo
words 'FAULT HISTORY' and the fault
code encountered. The bottom line
displays the date and time the fault
occurred.
This screen displays the second
oldest boiler control lockout fault.
The top line will alternate between
2
the words 'FAULT HISTORY' and
the actual fault encountered. The
bottom line will display the date
and time that the fault occurred.