Westinghouse Premium WBCMC 1000 Series Installation Manual page 44

Table of Contents

Advertisement

44
Function 19
BOILER SUPPLY DHW
o
180
F
19
Function 20
WATER SAFETY INPUT
WATER PRESSURE
20
Function 21
ERROR OUTD SENSOR
OFF
21
Function 22
ADJ BOILER OUTPUT
100%
22
Function 23
Top Boiler
CASCADE MODE
COMMON FLUE
23
Bottom Boiler
CASCADE MODE
2 BOILER
23
Function 24
CASCADE ROTATION
48 HOURS
24
Function 25
NOT USED
NOT USED
25
whl-428-r1 Rev. 001 Rel. 012 Date 7.21.20
Boiler DHW Temp
Allows the user to program the boiler
supply water temperature to the
indirect heat exchanger during a
o
demand cycle. Default: 180
F (Range:
o
o
119
F to 190
F).
Water Safety Input
The user can select various water
safety inputs used in the boiler system.
Default: Flow Switch (Range: None
/ Low Water Cut Off / Flow Switch /
Water Pressure).
Error Outdoor Sensor
Allows the user to set the control to
display an error message if an outdoor
sensor is open or shorted. NOTE: This
error does not stop the boiler from
running. Factory Default: OFF (Range:
ON / OFF / PHOEN ON).
Adjust Boiler Output %
Adjusts the boiler output down from
100% to 50%. Factory Default: 100%.
(Range: 100% – 50%)
Cascade Mode
Allows the user to select the cascade
mode. If one or more 1000 or 1700
units are cascaded in a common
vent manifold, select the number of
individual cascaded boilers in the
system on the cascade master (2
BOILERS if a single MOD CON 1700, 6
BOILERS if three MOD CON 1000s, etc.)
On cascade followers in a common
vent system, select COMMON FLUE
to establish a cascaded system WITH
common vent. Factory Default: 2
BOILERS on Cascade Master (bottom
boiler), COMMON FLUE on Cascade
Follower (top boiler). Range: ALL 926
/ 2 – 8 BOILERS [on cascade master
ONLY] / COMMON FLUE [on cascade
followers ONLY]). NOTE: All MOD
CON 1000 and 1700 boilers are to be
configured as COMMON VENT systems.
Cascade Rotation
Sets the amount of hours before the
first boiler in the cascade firing rotation
will be changed. NOTE: If this is set to 0,
the firing order of the boilers will not
rotate. Default: 48 hours (Range: 0 –
240 hours).
Cascade DHW Mode
Not applicable on this product.
Screen
Function 26
System Freeze Protection
NOTE: This parameter is only present
if the boiler is a cascade master. Allows
the user to set the freeze protection
SYS FREEZE PROT
when a system pump is used. Factory
PROTECT OFF
26
Default: OFF. Selection of temperature
activates freeze protection. (Range:
OFF, -40
Function 27
Error System Sensor
Sets the control to display an error
message if the system sensor is open
ERROR SYSTEM SENS
or shorted. NOTE: This error does
ON
27
not stop the boiler (or boilers) from
running. Factory Default: ON (Range:
ON / OFF).
Function 28
Freeze Protection
Allows the user to set freeze protection
FREEZE PROTECTION
on the boiler. Factory Default: ON
ON
28
(Range: ON / OFF).
Function 29
DHW Modulation Mode
This parameter controls how the
boiler modulates for a DHW demand.
In NORMAL MOD mode, the boiler
will modulate down from high fire
when there is a DHW demand. In LOW
MOD mode, the boiler will modulate
DHW MODULATE MODE
up from low fire when there is a
NORMAL MOD
29
DHW demand. This mode is useful to
minimize short cycling when a large
boiler and small indirect tank are used
together. Factory Default: NORMAL
MOD (Range: NORMAL MOD / LOW
MOD).
Function 30
Extra Boiler Mode
Allows for a non Westinghouse boiler
to be controlled when the cascade
EXTRA BOILER MODE
output has risen above the percent
OFF
30
of the cascade firing rate set in this
parameter. Factory Default: Off (Range:
50% - 100%).
Function 31
System Sensor Mode
Suppresses the 'NO FOLLOWER' display
message if the boiler is used as a
SYSTEM SENSOR MODE
cascade master boiler with no follower
OFF
31
boilers connected. Factory Default:
OFF (Range: ON / OFF).
Function 32
Service Schedule
Selects a service date or time based
on the boiler run hours to program
the boiler maintenance schedule.
SERVICE SCHEDULE
Factory Default: OFF (Range: Date or
OFF
32
Run Hours). NOTE: Without setting this
function, Functions 33/34/35/36 will
not display.
Description
o
o
F – 104
F).