Installing the WLAN Expansion
Installing and Wiring the Power Switch
Fig. 7:
Connection terminal, already installed
Pos. 1
Cover panel with RJ45 network sockets
Pos. 2
Cover panel for WLAN power switch
Pos. 3
Blank cover panel, short
Pos. 4
Blank cover panel, long
Pos. 5
Illustration of the power switch installation location
Pos. 6
Power cable ground wire to power outlet strip
Pos. 7
Power cable ground wire to the WLAN power supply
Installing the new Cover Panels on the Connection Terminal
•
The cover panel with the RJ45 network sockets
•
Remove the old cover panel(s) next to the cover panel with the RJ45 network sockets
on the connection terminal. The nuts and ground wire connections are needed again for
the following installation of new cover panels.
•
Install the new cover panel for the WLAN power switch
•
Install the new short
Installing the WLAN Power Switch
•
Press the power switch
switch from the outside. The installation location can be seen in
Wiring the WLAN Power Switch with the WLAN Power Supply
•
Lay the power cable coming from the WLAN power supply
power switch.
•
Plug in the cable with the designation S15.1A on the power switch
•
Plug in the cable with the designation S15.2A on the power switch
•
Cut open the heat-shrink tubing around the power cable and the trailing attached
ground wire and remove it.
•
Connect the ground wire to the connection terminal.
Wiring the WLAN Power Switch with the Power Outlet Strip
•
Lay the power cable
side cover panel and the monitor carriage up and into the top compartment.
Siemens
Medical Solutions
(3/Fig. 7 / p. 17)
(4/Fig. 2 / p. 13)
(6/Fig. 3 / p. 13)
DRAFT 22.04.2008
SP00-000.814.09.01.02
11.07
Fig. 8:
WLAN power switch wiring
Pos. 1
Power supply power cable 1 (power switch -
WLAN power supply)
Pos. 2
Power supply power cable 2 (power switch -
power outlet strip)
Pos. 3
Power cable 1 blue lead
Pos. 4
Power cable 1 brown lead
Pos. 5
Power cable 2 blue lead
Pos. 6
Power cable 2 brown lead
(1/Fig. 7 / p. 17)
(2/Fig. 7 / p.
and long
(4/Fig. 7 / p. 17)
into the cover panel for the WLAN power
(1/Fig. 8 / p. 17)
from the power outlet strip to the side between the
Page 17 of 78
CS PS SP
17
remains installed.
17).
blank cover panel.
(5/Fig. 7 / p.
17).
to WLAN
(3/Fig. 8 / p.
17).
(4/Fig. 8 / p.
17).
ARCADIS
0