Plug in the S15.1 cable on the power switch
•
Plug in the S15.2 cable on the power switch
•
Cut open the heat-shrink tubing around the power cable and the trailing attached
ground wire and remove it.
•
Connect the ground wire to the connection terminal.
•
Connect the attached power connector on the power cable to the existing power outlet
strip.
Laying out the Ground Wiring at the Connection Terminal
•
Lay out the grounding wires at the connection terminal as shown in
When doing this, also secure the ground wire connections for the new power cables.
See
Fig. 9:
Connection terminal, already installed
Pos. 1
Cover panel with RJ45 network sockets
Pos. 2
Cover panel for WLAN power switch
Pos. 3
Blank cover panel, short
Pos. 4
Blank cover panel, long
Pos. 5
Illustration of the power switch installation location
Pos. 6
Power cable ground wire to power outlet strip
Pos. 7
Power cable ground wire to the WLAN power supply
Labels with the Reference Symbol to the Operator Manual
•
Attach one of the labels with the warning symbol for non-ionizing radiation and a refer-
ence symbol to to the Operator Manual along side one another, below the WLAN power
switch.
•
Attach the 2nd label with the warning symbol for non-ionizing radiation and the 2nd ref-
erence symbol to the Operator Manual on the top console of the monitor carriage, cen-
tered between the base of the monitor base and the inset to store the mouse (= location
of the signal source below the console, centered to the signal antennas of the WLAN
Client).
ARCADIS
(6/Fig. 7 / p. 17)
and
(7/Fig. 7 / p.
Make sure that the ground wire connection coming from the monitor carriage is
securely connected.
Make sure that all ground wire connections have good contact.
DRAFT 22.04.2008
SP00-000.814.09.01.02
11.07
Installing the WLAN Expansion
(5/Fig. 8 / p.
(6/Fig. 8 / p.
17).
Fig. 10: Label with reference to the User Manual