Installation
Figure 39. Air-Fi terminal
Figure 40. Air-Fi wiring, ref. 50712792
RED
1X3-1
BLK
1X3-2
BLU
1X3-3
IMC
A
-
+
-
+
G
-
+
-
P1
P2
BACKNET
MODBUS
MACHINEBUS
1A22 SYMBIO 800 UNIT CONTROLLER
USB
1
2
3
4
LTE Modem Installation
Modem part is MOD03184, MODULE; CELLULABLE USB 2.9
METER CABLE. Refer to provided literature for setup and
operation details.
1. Drill a 1.36 inch holes on the top of polycarbonate box,
securely fasten the LTE modem by gasket and nut which
provided by modem.
2. Connect LTE modem to Symbio800 by USB cable which
provide by module, plug USB MICRO-B side to bottom of
LTE modem and USB-A side to any one of the four USB
ports under the Symbio800 controller.
24
OPTIONAL
4K48
AIR-FI
INTERFACE
IMC
+
G
+24
-
+
G
+24
B
VDC
VDC
IMC
P3
SERVICE
TOOL
ETHERNET
1
2
Figure 41. LTE modem wiring
OPTIONAL
1A22 SYMBIO 800 UNIT CONTROLLER
4Y2
LTE
MODEM
TRACER
COMMUNICATIONS
OPTIONAL

Communication Device Mounting

These devices are intended to be mounted on polycarbonate
boxes. There are two installation approaches:
Each device is mounted independently on a small box
(0185-0426-0100).
Multiple devices are mounted on a large box (0185-0427-
0100).
All devices connect Symbio 800 by standard USB or Modbus
cable. For installation, standard application need to field drill an
1.09-inch hole on side of box for a snap bushing. This bush can
be replaced as field straight connector and conduit (3/4 inch
size) as NEMA 4 applications.
The boxes have magnets for flexible attachment to the Symbio
panel.
Figure 42. Polycarbonate box with magnets
ETHERNET
USB
1
2
1
2
3
4
1K47
LON
INTERFACE
SO-SVN037A-EN