The meter is connected to line voltage of up to 480 volts and
should be mounted within the starter cabinet. It is provided with
a mounting bracket that can either be mounted on DIN rail or
directly to cabinet wall. It is mountable using the provided
bracket.
Figure 52. Mount energy meter with strap tunnel on rail
The meter is connected to Modbus communications and is
self-powered by the unit voltage potential inputs. Review meter
literature for setup and operation details.
Modbus communications is by shielded 14 – 26 AWG cable
from meter to Symbio module. Install 120 OHM resistors at first
and last modules on Modbus daisy chain.
Figure 53. Sheilded cable
+
S
Shielded Wire
120 terminators on the first/last devices of daisy
Ω
The communications wiring will be terminated at the Modbus
distribution terminal (1X3) beside Symbio 800 using the 3
poles connector which provide in energy meter kits.
Figure 54. Modbus distribution terminal
SO-SVN037A-EN
chain
Figure 55. Communication wiring, ref. 50712792
OPTIONAL
ENERGY METER
OPTIONAL
4Y1
WI-FI
ANTENNA
480 Volts and Lower Installations
POTENTIAL INPUT – Install provided fused inputs to line
voltage per schematic.
CURRENT INPUT – Install provided Rogowski CTs per
schematic.
Figure 56. 480V Energy meter wiring, ref. 50712756
ENERGY METER OPTION
2T50
T
T
T
T
T
T
X1 X2
L1
2P25
ENERGY METE R
(E23)
2F1 LINE SIDE
T
2F2 LINE SIDE
T
2F3 LINE SIDE
T

Expansion Module Option

CDUB retrofit panel reserve place of expansion module beside
Symio 800 controller. There are few configurations that
depend on I/O requirements and din rail length. Currently din
rail in CDUB panel is 13.9 inch, could add one XM32 or two
XM30 at most. If XM70 is selected, a 20-inch din rail is
required, in 0185-3495-0100. For detailed I/O information,
refer to 50712794.
Installation
RED
1X3-1
BLK
1X3-2
BLU
1X3-3
IMC
A
-
+
-
+
G
-
P1
P2
BACKNET
MODBUS
DETAIL A
TO 1X3
LINE 99
2T51
2T52
X1 X2
X1 X2
+
-
G
L2
L3
MODBUS
CT INPUT S
VOLT INPUTS
L1
L2
L3
N
2F52
0.5A
2F53
0.5A
2F54
0.5A
+
27