Component
P1 ground
P1-9 and ground
connection
Low oil
P1-15 and engine
pressure
block (ground)
(LOP) safety
NOTE: J4 and P4 must
shutdown
be connected to
switch
perform this test.
High water
P1-15 and engine
temperature
block (ground)
(HWT) safety
NOTE: LOP switch
shutdown
lead should be removed
switch
and isolated.
NOTE: J4 and P4 must
be connected to
perform this test.
Rotor
See separate paragraph
with same title.
Stator
See separate paragraph
with same title.
Excitor Field
See separate paragraph
with same title.
Excitor Armature
See separate paragraph
with same title.
Fuel Solenoid
See separate paragraph
with same title.
Figure 7-9. Engine/Generator Set Component Testing with Ohmmeter (Sheet 2 of 2)
TP-5648 8/93
Ohmmeter
Connections
Ohmmeter on R x 1
scale.
Ohmmeter on R x 1
scale.
This test is not
conclusive until the
temperature shutdown
switches are checked.
Ohmmeter on R x 1
scale.
See separate paragraph
with same title.
See separate paragraph
with same title.
See separate paragraph
with same title.
See separate paragraph
with same title.
See separate paragraph
with same title.
Remarks
If good--zero ohms
(continuity). Any other
reading indicates a poor
ground connection.
If good--zero ohms
(continuity). Then,
disconnect LOP switch lead
and isolate terminal. Meter
reading reading should
show an open circuit.
If good--open circuit.
Any continuity suggests
that temperature switch(es)
are defective. Disconnect
individual leads to determine
which switch is defective.
See separate paragraph
with same title.
See separate paragraph
with same title.
See separate paragraph
with same title.
See separate paragraph
with same title.
See separate paragraph
with same title.
Component Testing and Adjustment 7-13