Kohler 10CCOZ61 Service Manual page 45

Mobile generator sets
Table of Contents

Advertisement

Problem
Generator
set shuts
down by
itself
(cont' d.)
High water temperature
Low oil pressure switch,
high engine temperature
Problem
Will not
carry load
or runs
rough
Governor not properly
adjusted or defective
(Engine not operating
4-6 General Troubleshooting
Possible Cause
No/low oil pressure
shutdown
switch
Possible Cause
Excessive load
connected to
generator
Improper cooling
(hot engine only)
at rated rpm)
Engine in need
of overhaul
Corrective Action
Check oil level, oil
pressure, oil pump,
and low oil pressure
shutdown switch
Check engine cooling
system
Disconnect lead from one switchand isolate
the lead from ground. If engine continues to run, replace
hat switch.
NOTE: Verify proper pressure, or temperature
before replacing switch.
Corrective Action
Reduce electrical load
Inspect cooling system
Check speed using
tachometer or
frequency meter.
NOTE: For 60 Hz--1800 RPM
For 50 Hz--1500 RPM
Contact Kohler
distributor
Reference
Engine Service Manual
Engine Service Manual
Reference
Section 3. Wattage
Requirements
Section 3. Cooling System
Section 3. Governor
Engine Service
Distributor
TP-5648 8/93