WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Use protective goggles and clothes.
permanent damage to eyes, burn skin, and eat holes
in clothing.
Sulfuric acid in batteries can cause severe injury or
death. Sulfuric acid in battery can cause permanent
damage to eyes, burn skin, and eat holes in clothing.
Always wear splash-proof safety goggles when working
around the battery. If battery electrolyte is splashed in
the eyes or on skin, immediately flush the affected area
for 15 minutes with large quantities of clean water. In the
case of eye contact, seek immediate medical aid. Never
add acid to a battery once the battery has been placed in
service. Doing so may result in hazardous spattering of
electrolyte.
Explosion can cause severe injury or death. Battery
gases can cause an explosion. Do not smoke or permit
flame or spark to occur near a battery at any time,
particularly when it is being charged. Avoid contacting
terminals with tools, etc. to prevent burns and to prevent
sparks that could cause an explosion.
wristwatch, rings, and any other jewelry before handling
battery. Never connect negative (--) battery cable to
positive (+) connection terminal of starter solenoid. Do
not test battery condition by shorting terminals together
or sparks could ignite battery gases or fuel vapors. Any
compartment containing batteries must be well
ventilated to prevent accumulation of explosive gases.
To avoid sparks, do not disturb battery charger
connections while battery is being charged and always
turn
charger
off
before
connections.
When disconnecting battery, remove
negative lead first and reconnect it last.
1. Disconnect plug P5 of wiring harness from P1 on
voltage
regulator.
disconnect plug P7.
7-2 Component Testing and Adjustment
Can cause
Remove
disconnecting
battery
See
Figure 7-1.
Also
1. Plug P1
Figure 7-1. PowerBoostä V
Voltage Regulator
2. Connect an ammeter and a 12-volt automotive
battery to the positive (+) and negative (-) brush
leads. Include a 10-amp. fuse to protect the circuit
in case of a shorted rotor. Refer to Figure 7-2.
Note and record the ammeter reading.
10-Amp
Fuse
DC
AM
--
+
12 Volt
Battery
Figure 7-2. Separate Excitation Connections
1
8
7
6
5
4
3
2
1
1-850
To Controller
P5--12
P4
P4
P5--10
P6
P7
Excitor
Field
TP-5648 8/93