Section 7. Refrigerant Line Brazing

7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a deburing tool to debur the pipe ends. Clean both internal and external
surfaces of the tubing using an emery cloth.
STEP 2 - Remove the pressure tap cap and valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
Note: Install drier in Liquid Line.
N N OTE:
OTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to
Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to
keep the flame directly off of the basepan.
keep the flame directly off of the basepan.
STEP 5 - Replace the pressure tap valve cores after the service valves have cooled.
STEP 1
STEP 4
8
3-4" from valve
STEP 2
STEP 5
STEP 3