5803641-JIM-B-0620
Table 29: Smart Equipment™ UCB Details (Continued)
SAT+
RAT+
OAT+
CC1+
EC1+
CC2+
EC2+
RAH+
DCT PRS+
DFS (upper pin)
DFS (lower pin)
APS (upper pin)
APS (lower pin)
C
54
Description
Supply Air Temperature sensor input from 10KΩ
@ 77°F, Type III negative temperature coefficient
thermistor
Return Air Temperature sensor input from 10KΩ
@ 77°F, Type III negative temperature coefficient
thermistor
Outside Air Temperature sensor input from 10KΩ
@ 77°F, Type III negative temperature coefficient
thermistor
#1 refrigerant circuit Condenser Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
#1 refrigerant circuit Evaporator Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
#2 refrigerant circuit Condenser Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
#2 refrigerant circuit Evaporator Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
Pinned connections on right edge of UCB
Return Air Humidity input from 0-10 VDC @ 0-
100% RH sensor
Supply Duct Pressure input from 0-5 VDC @ 0-5"
w.c. sensor
24 VAC hot return from Dirty Filter Switch
24 VAC hot out for Dirty Filter Switch
24 VAC hot return from Air Proving Switch
24 VAC hot out for Air Proving Switch
Common for the VFD output
Function & Comments
Input required for operation; 3.625 VDC reading SAT+ to SAT–
with open circuit. Used in heat/cool staging cutouts, free cooling
operation, demand ventilation operation, comfort ventilation
operation, economizer loading operation, VAV cooling
operation, hydronic heat operation.
Input required for operation; 3.625 VDC reading RAT+ to RAT–
with open circuit. Used in return air enthalpy calculation.
Substitutes for space temperature if no other space
temperature input is present.
Input required for operation but may be a communicated value;
3.625 VDC reading OAT+ to OAT– with open circuit. Used in
heat/cool cutouts, low ambient cooling determination, dry bulb
free cooling changeover, outside air enthalpy calculation,
economizer loading operation, heat pump demand defrost
calculation.
Input required for heat pump units, not required for A/C units;
3.625 VDC reading CC1+ to CC1– with open circuit. Used in
heat pump demand defrost calculation.
Input required for operation; 3.625 VDC reading EC1+ to EC1–
with open circuit. Used in suction line temperature safety.
Input required for 2-compressor heat pump units, not required
for 2-compressor A/C units, not active for 1-compressor units;
3.625 VDC reading CC2+ to CC2– with open circuit. Used in
heat pump demand defrost calculation.
Input required for operation of 2-compressor units, not active for
1-compressor units; 3.625 VDC reading EC2+ to EC2– with
open circuit. Used in suction line temperature safety.
Input required for reheat units, optional in all other units, may be
a communicated value. Used in return air enthalpy calculation,
temperature/humidity setpoint reset, reheat operation.
Input required for variable air volume units. Used in VAV indoor
blower operation.
Optional input; switch closure for greater than 15 seconds
during indoor blower operation initiates a notification alarm
Connects through circuit trace to the R terminal
When this optional input is enabled: the air proving switch must
close within 30 seconds of initiation of indoor blower operation
and not open for greater than 10 seconds during indoor blower
operation to allow heat/cool operation and prevent an "APS
open" alarm; the air proving switch must open within 30
seconds of termination of indoor blower operation to prevent an
"APS stuck closed" notification alarm
Connects through circuit trace to the R terminal
Negative of the VDC circuit for the VFD output