Riello 20047690 Installation, Use And Maintenance Instructions page 15

Premix gas burners
Table of Contents

Advertisement

Technical data
LME71... burner con-
Mains voltage
Mains frequency
trols
Power consumption
External primary fuse
Safety class
Terminal rating
Under voltage
"Inputs"
Input currents and input voltages
Voltage detection
Terminal rating
Total contact loading:
"Outputs"
Rated voltage
Unit input current X3-04 (safety loop) from:
Individual contact loading:
Fan motor contactor X2-01 pin 3
Alarm output X2-03/3
Ignition transformer X4-02 pin 3
Auxiliary output
Output relay contact 2 pin 2 X2-09 pin 7
Fuel valves/pilot valve X7-01 pin 3
Safety valve X6-03 pin 3
Cable lengths
Mains supply line
Cross-sectional
The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, the safety loop (safety limit
areas
thermostat, water shortage, etc.) must be sized for rated currents according to the selected external primary
fuse. The cross-sectional areas of the other cables must be sized in accordance with the internal unit fuse (max.
6.3 AT).
Environmental
Operation
conditions
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Technical description of the burner
Safety shutdown from the operating position takes
place should mains voltage drop
Restart is initiated when mains voltage exceeds
UeMax
UeMin
IeMax
IeMin
ON
OFF
fan motor contactor
ignition transformer
fuel valves
Rated voltage
Rated current
Power factor
Rated voltage
Rated current
Power factor
Rated voltage
Rated current
Power factor
Rated voltage
Rated current
Power factor
Rated voltage
Rated current
Power factor
Rated voltage
Rated current
Power factor
Rated voltage
Rated current
Power factor
AC 120 V
50 / 60 Hz
<10 W, typical
Max. 6.3 A (slow)
I with parts according to II and III to DIN EN 60730-1
UMains 120 V
< AC 75 V
> AC 100 V
UN +10%
UN -15%
1.5 mA peak (peak value)
0.8 mA peak (peak value)
> AC 60 V
< AC 40 V
AC 120 V - 50/60 Hz
Max. 5 A
AC 120 V 50/60 Hz
2 A (15A max. 0.5 s)
Cos   0.4
AC 120 V 50/60 Hz
1 A
Cos  > 0.6
AC 120 V 50/60 Hz
2 A
Cos  > 0.4
AC 120 V 50/60 Hz
1 A
Cos  > 0.6
AC 120 V 50/60 Hz
1 A
Cos  > 0.4
AC 120 V 50/60 Hz
1 A
Cos  > 0.4
AC 120 V 50/60 Hz
1.5 A
Cos  > 0.6
Max. 100 m (100 pF/m)
DIN EN 60721-3-3
Class 3K3
Class 3M2
-40...+60 °C
<95% r.h.
13
GB
Tab. G
20051011