Complete the following steps:
1. Back up data.
2. Check the current Intel Optane PMEM DIMM health status in one of the following ways:
a. Run PMEM test under LXPM diagnostic. Look for "Percentage Remaining" of spare blocks.
b. Check for "Remaining Life" of spare blocks on the XCC Web GUI.
3. Check if the PMEM meets warranty terms.
a. If the PMEM meets the warranty terms, contact Lenovo Support for PMEM replacement.
b. If the PMEM does not meet the warranty terms, order a new comparable PMEM through an
authorized Lenovo reseller.
4. Collect Service log and contact Lenovo support to schedule PMEM replacement.(Note: Unless
otherwise specified in other agreements or contract terms, parts beyond their warranty terms and/or
parts that have reached their maximum usage limitations do not qualify for warranty service.)
• FQXSFMA0033M: Intel Optane PMEM persistent memory interleave set has [arg1] PMEMs(DIMM
[arg2]), [arg3] DIMMs' location is not correct.
Severity: Warning
User Action:
Complete the following steps:
1. Collect XCC Service Data.
2. Power off system.
3. The following error message FQXSFMA0034M logs will provide the correct location for PMEMs.
4. Move all PMEMs of error message FQXSFMA0034M logs to the correct location.
5. If the problem persists, collect Service Data logs and contact Lenovo Support.
• FQXSFMA0034M: DIMM [arg1] (UID: [arg2]) of Intel Optane PMEM persistent memory interleave set
should be moved to DIMM slot [arg3] in sequence.
Severity: Warning
User Action:
Complete the following steps:
1. Collect XCC Service Data.
2. Power off system.
3. Details included in this error message will provide the correct location for that PMEM.
4. Move the PMEM to the correct location.
5. If the problem persists, collect Service Data logs and contact Lenovo Support.
• FQXSFMA0035M: Intel Optane PMEM interleave set should have [arg1] PMEMs, but [arg2] PMEMs
are missing.
Severity: Warning
User Action:
Complete the following steps:
1. Collect XCC Service Data.
2. Power off system.
3. The following error message FQXSFMA0036M logs will provide the details which PMEMs are
missing.
158
ThinkSystem SR860 V2 Messages and Codes Reference