Ups Input And Output Overview - Tripp Lite SmartOnline SUPDMB5 Owner's Manual

Single-phase rack-mount online ups with built-in lcd monitoring, control screen and detachable bypass power distribution module
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
Installation

UPS Input and Output Overview

Model Name
SUPDMB5
SUPDMB5P
SUPDMB5G
SUPDMB5HW
SUPDMB6
SUPDMB6P
SUPDMB6IEC
SUPDMB6G
SUPDMB6HW
Input
Input Line
Connection
Configuration
HW
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
HW
L, N, PE
HW
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
Building Breaker
C-Curve
Input AWG (mm
40
30
30
40
40
50
30
30
50
50
50
16
Receptacle Plate
)
Configuration
2
8 (6)
10 (4)
10 (4)
8 (6)
8 (6)
None
6 (10)
10 (4)
10 (4)
6 (10)
6 (10)
6 (10)