Section 2: Framing; In Wall And Corner Dimensions; Alcove Dimensions - Montigo Phenom PL38 Installation & Maintenance Manual

Hide thumbs Also See for Phenom PL38:
Table of Contents

Advertisement

Section 2: Framing

In Wall and Corner Dimensions

A
B
C
Noncombustible
Stud
Figure 3.b Framing dimensions (Straight wall & Corner Installation).
P38, PL38
A
37 ¾''
B
34 ¼''
C
41 ¼''
D
20 ⅛''
E
76 ¼''
F
37 ¾''
G
53 ⅞''
P42, PL42
A
42''
B
35''
C
42''
D
21 ⅞''
E
84 ½''
F
42''
G
59 ¾''
XG0199 - 170223
G
D
NOTE: When constructing the
framed opening, please ensure
there is access to install the gas
line when the unit is installed.
P52, PL52
A
52''
B
37 ½''
C
43 ¾''
D
24 ½''
E
98''
F
52''
G
64 ¼''
WARNING
When this appliance is installed directly on ANY combustible other
than wood flooring (carpet, vinyl, etc.). It must be installed on an
equivalent wood or metal panel. This material must extend the full
width and depth of the appliance.
NOTICE
Clearances must be in accordance with local installation codes and
the requirements of the gas supplier
Alcove Dimensions
B
Rear
A
Vent
(NG only)
NOTE: P52
and PL52
cannot be
rear vented
straight out
a wall.
Figure 3.b.b Non Combustible Framing for Top Vent or Rear Vent, with alcove.
P38, PL38, P42, PL42
A
96'' MIN
B
12'' MAX
C
1'' MIN
D
3''
E
12"
F
37 ⅝"
Installation
Ceiling
Alcove area
over Fireplace
Non-Combustible
Materials Only
C
Non-combustible
header
D
E
F
Door
opening
Floor
P52, PL52
A
84'' MIN
B
N/A
C
1'' MIN
D
1 ¼''
E
11½"
F
39 ¼''
9