Heat Shields 5''/10'' (For P52Df And Pl52Df) - Montigo Phenom PL38 Installation & Maintenance Manual

Hide thumbs Also See for Phenom PL38:
Table of Contents

Advertisement

Heat Shields 5''/10'' (For P52DF and PL52DF)
Installing a Wall Mounted RHS102 Heat shield
The RHS102 Heat Shield (Figure 16 and 16a) MUST be used in all
cases where the venting passes through a wall. To install the RHS 102,
frame an opening in combustible construction. Slide the Heat shield
in place over the vent pipe which attaches to the fireplace. After the
fireplace and vent pipe has been installed, clearances should match
the dimensions in Figure 16.
1/4'' min.
1/4'' min.
Figure 16. RHS102 Installation.
RHS 102 Heat Shield
RHS 102 Heat Shield
Outer Section
Outer Section
Figure 16.b RHS102 Installation.
5''/10''
27" Min
Figure 16.c RHS 102 & RHS 104 Installation. (Minimum requirements).
28
1/4'' min. Both sides Typical
Inner shield 11 1/2''
Outer shield 10 5/8''
Combustible Framing
Drywall/Sheetrock
Drywall / sheetrock
RHS 102 Heat Shield
RHS 102 Heat Shield
Inner Section
Inner Section
Vent pipe
Vent Pipe
Combustible
Combustible
Framing
framing
36" Min
RHS104 Heat Shield
Inner Section
RHS102
RTO-4F Termination
Heat
60 Min"
Shield
Installing a Wall Mounted RHS104 Heat shield
Installing a Wall Mounted RHS 104 Heat shield. The RHS104 Heat shield
MUST be used in conjunction with the RTO-4F Termination (Figure 16
and 16b).
To install the RHS104, Slide the Inner Section over the vent pipe.
From the outside slide the RHS104 outer section on (see Figure 16f).
To complete the installation fasten the Heat Shield Outer Section &
Termination frame to the structure.
1 1/4'' min.
1 1/4'' min.
Figure 16.d RHS104 Installation
RHS101 Heat Shield Outer Section
Termination
Figure 16.e RHS104 Installation.
36" Min
5''/10''
27" Min
RHS102
Heat
Shield
Figure 16.f RHS 102 & RHS 104 Installation. (Minimum requirements).
Installation
1 1/4'' min. Both sides Typical
Inner shield 11 1/2''
Outer shield 10 5/8''
Combustible Framing
Drywall / sheetrock
RHS101 Heat Shield, inner Section
Vent pipe, from fireplace
Combustible framing
RHS104 Heat Shield
RTO-4F Termination
60 Min"
XG0199 - 170223