UV scanner
In order to reach the UV scanner, proceed as follows:
Extract the UV scanner 2).
Clean the glass cover from any dust that may have accumu-
lated.
6.3
Opening the burner
Disconnect the electrical supply from the burner by
means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Wait for the components in contact with heat sourc-
es to cool down completely.
20097716
Maintenance
2
1
37
2
20086820
To open the burner proceed as follows:
switch off the electrical power;
loosen screws 1) and withdraw the cover 2);
disengage the swivel coupling 7) from the graduated sector;
disconnect the light-oil pipes 8);
remove screws 3) and pull the burner back by about 4" on the
slide bars. disconnect the electrode leads.
Install the extension bars 31)(Fig. 5, page 11) and re-screw
the 2 screws and the safety plate Fig. 12, page 18.
Pull the burner fully back.
Now extract the internal part 5) after having removed the screw 6).
3
4
8
GB
6
8
5
7
Fig. 52
Fig. 53
20095062