Flame presence check
The burner is fitted with an ionisation system to check that a
flame is present. The minimum current for flame control operation
is 6 µA (Fig. 32).
The burner provides a much higher current, so controls are not
normally required.
However, if it is necessary to measure the ionisation current, dis-
connect the plug-socket on the ionisation probe cable and insert
a direct current microammeter with a base scale of 100 µA.
Carefully check the polarities!
D3097
Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
Gas filter
Replace the gas filter when it is dirty.
Combustion
If the combustion values measured before starting maintenance
do not comply with applicable legislation or do not indicate effi-
cient combustion, consult the Tab. O or contact our Technical
Support Service to implement the necessary adjustments.
It is advisable to set the burner according to the type of gas used
and following the indications in Tab. O.
7.3

Opening the burner

Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
7.4

Closing the burner

Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled.
Carry out all maintenance work and mount the
casing again.
A
-
+
Fig. 32
31
EN 676
CO
CO
theoretic
2
GAS
al max. 0% O
 = 1.2
2
G 20
11.7
G 25
11.5
G 30
14.0
11.6
G 31
13.7
11.4
7.2.4

Safety components

The safety components should be replaced at the end of their life
cycle indicated in the Tab. P. The specified life cycles do not refer
to the warranty terms indicated in the delivery or payment condi-
tions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic cam)
Oil valve (solenoid)
Oil regulator
Pipes/ oil fittings (metallic)
Fan impeller
Wait for the components in contact with heat
sources to cool down completely.
see "Access to head internal part" on page 17.
GB
Air excess
Max. output
Min. output
 1.2
 1.3
% Calibration
CO
2
= 1.3
mg/kWh mg/kWh
9.7
9.0
 100
9.5
8.8
 100
10.7
 100
10.5
 100
Life cycle
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
15 years
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years
10 years or 500.000 start-ups
NO
X
 170
 170
 230
 230
Tab. O
Tab. P
20160598