Flame Signal Measurement; Final Checks (With The Burner Working) - Riello RLS 100/E Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burners
Table of Contents

Advertisement

5.7

Flame signal measurement

Check the flame signal through the parameter 954, as indicated in
Fig. 50. The displayed value is expressed in percentage.
The value during the operation must be higher than 24%. If at the
burner start-up the value is higher or equal of 18%, the burner locks
out due to the extraneous light.
For further and specific information, please refer to the specific in-
struction manual.
The display (Fig. 50) shows parameter 954: flashing on the left.
On the right, the flame's intensity is displayed as a percentage.
Example: 954: 0.0
5.8

Final checks (with the burner working)

 Open the control limit operation
 Open the high limit operation
 Rotate the maximum gas pressure switch knob to the mini-
mum end-of-scale position
 Rotate the air pressure switch knob to the maximum end of
scale position
 Rotate the maximum oil pressure switch at the minimum of
the scale
 Switch off the burner and disconnect the voltage
 Disconnect the minimum gas pressure switch
 Rotate the minimum low oil pressure switch at the maximum
of the scale
 Cover the UV flame sensor
Make sure that the mechanical locking systems on
the different adjustment devices are fully tightened.
WARNING
Start-up, calibration and operation of the burner
35
S8171
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to firing failure
GB
P
V
h min s
%
Fig. 50
20095062