Afterwards you can initialize the device by loading the parameterization. Before going to the
chapter
9.3.3 Initializing device and verifying basic
Project with DIGSI
NOTE
i
i
If you find another default display after device startup, then someone before you has initialized the device.
You can now load your parameterization to the device. In the DIGSI 5 project tree, use the Load Configura-
tion in Device menu item.

Using a Project with DIGSI 5

9.3.2
All settings of the device are created with the DIGSI 5 operating program. The engineering department is
responsible for editing. In the respective project (see chapter
the project-specific settings. Familiarize yourself with the project and the device settings before you execute
the next steps.
Take the following procedure as your guide:
Install the DIGSI 5 operating program on your PC/laptop. For commissioning, Siemens recommends the
²
DIGSI 5 variant Premium.
Accept the project from the engineering department and save it.
²
Open the project and the devices in it.
²
Check whether inconsistencies are shown. DIGSI 5 constantly performs a consistency check. If inconsis-
²
tencies are detected, the corresponding position in the operating program is marked. If this is the case,
clarify the cause.
Look into device-specific parameterization. Use the sequence described below as your guide.
²
Procedure for checking device parameterization:
Check whether the parameterized hardware coincides with the existing devices. In the project, click
²
Devices and networks.
If you communicate via Ethernet, check the correct setting of the IP addresses simultaneously. You can
²
also do these checks under Device.
If the project is an IEC 61850 system, go to menu item IEC 61850 GOOSE Communication to familiarize
²
yourself with the respective circuitry. If you use circuiting you can view the static reports on the systems
control.
Create an overview of the settings or the routing in the individual menu items. Siemens recommends
²
doing this when opening the device in DIGSI.

Initializing device and verifying basic status

9.3.3
SIPROTEC 5 devices are initialized via the front USB interface. Alternatively, you can initialize
SIPROTEC 5 devices via port J and SIPROTEC 5 Compact devices via port F. If you connect port J to a network,
you must change the previous IP address.
Connect the device to the corresponding USB interface of your computer.
²
In the DIGSI 5 operating program right-click on the device to be initialized.
²
Click on the Load Configuration in Device menu item.
²
DIGSI 5 then accepts the connection to the device and loads the complete parameterization into the device.
This process takes some time.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-J, Edition 07.2022
5.
status, read the information in the chapter
6 Using DIGSI
5) you will find the devices with
Commissioning
9.3 Initial Startup
9.3.2 Using a
241