Operation in the Operating State
8.5 Logs
Deletability
The fault log of your SIPROTEC 5 device can be deleted. For more details about this, refer to chapter
8.5.13 Saving and Deleting the
Reading on the Device through the On-Site Operation Panel
To reach the fault log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Fault logs
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[sc_faullg, 1, en_US]
Figure 8-17
Configurability
The indication scope of the fault log is configured in a specifically defined column of the information routing
(matrix) of DIGSI 5:
Target → Log → Fault log column
Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.
The operational measured values and the measured values of the fundamental components and symmetrical
components (see Device Manual) are calculated every 9 cycles (at 50 Hz, this is every 180 ms). However, this
can mean that the data are not synchronized with the sampled values of the analog channels. The recording
of these measured values can be used to analyze the slowly changing processes.
8.5.4

Switching-Device Log

Statistic values and position changes for switching devices such as circuit breakers and disconnectors are
logged in the switching-device log. Up to 2000 indications can be stored in the switching-device log.
Reading from the PC with DIGSI 5
To reach the switching-device log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Switch. device log
The statuses of the switching-device log last loaded from the device is shown to you.
To update (synchronization with the device) click the button Read log entries in the headline of the indi-
cation list
(Figure
178
Logs.
Reading the Fault Log on the On-Site Operation Panel of the Device
8-18).